6.3.12 Initial RPM Setup

 

C

TM

 

 

 

INITIAL RPM SETUP

 

 

WARMUP RPM

 

WAIT FOR LOAD RPM

 

 

RUN LOADED RPM

 

 

COOLDOWN RPM

 

___________________________________

00600

___________________________________

▼▲

ENTER-EDIT

▼ ▼

MORE MENUS

Initial RPM Setup Screen

a)Assign value for Warmup RPM.

b)Assign value for Wait to Load RPM.

c)Assign value for Run Loaded RPM.

d)Assign value for Cooldown RPM.

6.3.13 Miscellaneous Setup

 

C

TM

 

 

MISCELLANEOUS SETUP

 

NUMBER OF CRANK ATTEMPTS

PORT 1

SLAVE ADDRESS

 

PORT 1

RS432/RS485

 

PORT 1

RESPONSE DELAY

 

PORT 1 BAUD RATE

___________________________________

 

00003

___________________________________

▼▲

ENTER-EDIT

 

▼ ▼

MORE MENUS

 

Miscellaneous Setup Screen

User can access and edit the miscellaneous settings.

a)Crank Attempts: Define a value for number of crank attempts after which an over-crank sequence will be trig- gered in the Event logic.

b)Controller Slave Address: Provide the value for the Modbus Address Port. The factory default is 1.

c)Port 1 Mode: Select Communication Port 1 as RS232, or RS485.

d)Port 1 Reply Delay: To ensure sufficient time for the Modbus reply, assign appropriate time value for Delay Modbus Reply Port 1.

e)Port 1 Baud Rate: Select appropriate transmission baud rate

f)Port 2 Mode: Select Communication Port 2 as RS232, or RS485.

g)Port 2 Reply Delay: To ensure sufficient time for the Modbus reply, assign appropriate time value for Delay Modbus Reply Port 2.

h)Port 2 Baud Rate: Select appropriate transmission baud rate

i)Flywheel Teeth: Define a value for Flywheel Teeth used to calculate RPM.

The following cold temperature offset values should only be adjusted by personnel with a full working knowledge of the Centurion in conjunction with calibrated reference equipment.

j)Core Cold Temp Offset: Enter a non-zero Value for Core Temperature Adjustment (in tenths) to adjust the temperature readings for all Thermocouple inputs on both the Main I/O Module (C3-1). Entering a non-zero value will adjust the Cold Junction Compensation reading used to calculate temperature.

k)Exp Cold Temp Offset: Enter a non-zero Value for Expansion Board Temperature Adjustment (in tenths) to adjust the temperature readings for all Thermocouple inputs on Expansion I/O (C3-2). Entering a non-zero value will adjust the Cold Junction Compensation reading used to cal- culate temperature.

l)Hour Meter: The user may make hour meter adjustments. The range is 0 – 65535 hours.

CE-05171N page 31 of 44

Page 31