Vent or Chimney

Each opening must be at least 100 sq. in. or 1 sq. in. per 1000 Btuh of total input rating, whichever is greater. See minimum area per table.

12" Max.

Each opening

 

Vent or

 

Chimney

to outside must

 

 

 

 

be at least

 

 

 

1 sq. in. per

 

 

 

4000 Btuh of

 

 

 

total input

 

 

 

rating.

 

 

 

-

12"

Max

 

 

Furnace

Furnace

12" Max.

 

Water Heater

 

 

 

 

 

 

Minimum

 

 

Total Input

Free Area

Round Duct

Rating (Btuh) (Each Opening)

Diameter

40,000

100 sq. in.

12"

60,000

100 sq. in.

12"

80,000

100 sq. in.

12"

Figure 9. Equipment in a Confined Space with all Combustion Air drawn from Inside

Ventilation Louvers at each end of attic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12" Max

 

 

Water Heater

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum

 

 

Total Input

 

 

Free Area

Round Duct

Rating (Btuh)

(Each Opening)

Diameter

40,000

10 sq. in.

4"

60,000

15 sq. in.

5"

80,000

20 sq. in.

5"

100,000

25 sq. in.

6"

120,000

30 sq. in.

6"

140,000

35 sq. in.

7"

160,000

40 sq. in.

8"

Figure 10. Equipment in a Confined Space

with all Combustion Air drawn from

Outdoors through Exterior Wall

Vent or

Chimney

Attic

Insulation

Furnace

Water Heater

Air Duct must be at least 1 sq. in. per 4,000 Btuh of total input rating.

Ducts must extend above attic insulation.

Air Duct must be at least 1 sq. in. per 4,000 Btuh of total input rating.

12" Max

 

Vent or

 

 

Chimney

 

 

Ventilation Louvers

 

(each end of attic)

 

-

 

 

Outlet

NOTE: Air open-

 

Air

ings shall each

 

Water

have a free area

Furnace

of not less than

Heater

one square inch

 

 

 

per 4,000 Btuh of

Alternate

 

the total input rat-

Inlet Air

ing of all equipment

Air Inlet

in the enclosure.

 

-

 

 

Minimum

 

Total Input

Free Area

Round Duct

Rating (Btuh)

(Each Opening)

Diameter

40,000

10 sq. in.

4"

60,000

15 sq. in.

5"

80,000

20 sq. in.

5"

100,000

25 sq. in.

6"

120,000

30 sq. in.

6"

140,000

35 sq. in.

7"

160,000

40 sq. in.

8"

Figure 11. Equipment in a Confined Space

with all Combustion Air drawn from Outdoors through Vertical Ducts – from Ventilated Attic

-

-

Ventilation Louvers For

Unheated Crawl Space

Figure 12. Equipment in a Confined Space

with all Combustion Air drawn from

Outdoors through Ventilated Crawl Space

and Ventilated Attic

12

Page 12
Image 12
Nordyne G6RL 90+, G6RC 90+, G6RD 93+ installation instructions Minimum, Free Area, 40,000 100 sq. 60,000 80,000