Nordyne G6RL 90+ Drainage Of Condensate From Furnace, Elbow Combustion Air Intake, G6RC & G6RD

Models: G6RD 93+ G6RC 90+ G6RL 90+

1 36
Download 36 pages 42 Kb
Page 21
Image 21
Elbow

Elbow

Combustion

Air

Intake

Exhaust

Vent

1"

18" Min.

Exhaust 36" Max.

A

A

Exhaust

Plumbing Vent Roof Boot (Typ. Both Pipes)

A= 12" Above Roof or Snow Accumulation Level

Figure 20. Vertical Vent Termination

DRAINAGE OF CONDENSATE FROM FURNACE

The condensate drainage system is internal to the furnace. The drain may exit either the right or left side of the furnace cabinet. For a right side drain simply extend the tubing out of the 7/8" hole in the cabinet, see Figure 21.

For a left side drain follow the steps below:

1.Loosen the clamp on the soft exit tube (see Figure 21.)

2.Rotate the soft exit tube (counter clockwise, 180° upflow G6RC/RD models; clockwise 90° downflow G6RL models.)

3.Re-tighten the clamp. MAKE SURE CLAMP IS TIGHT TO AVOID LEAKAGE OF CON- DENSATE.

4.Route the tubing out of the 7/8" hole located 8 inches up from the bottom furnace.

The condensate should drain from the plastic collector box (location A in Figure 21) as droplets or a small stream. If you notice the furnace has operated for more than 5 minutes without drain- ing or the red status light on the control board is pulsing a 2-blink code follow the steps below.

1.Remove the collector box soft tube at loca- tion A in Figure 21 and insure the exit from

G6RC & G6RD

G6RL

A

A

 

 

Collector Box

 

Collector Box

 

 

 

 

Left

 

 

 

 

 

 

Side

Rotate clockwise

Left Side

Rotate counter

 

Drain

Drain

 

 

 

(Step 2)

clockwise (Step 2)

Route to

 

 

 

 

 

 

 

 

 

floor drain.

 

 

 

8"

 

 

...OR

8"

 

 

 

 

Route to

 

 

 

 

 

 

 

 

 

 

 

condensate

 

 

 

"HARD" J

 

Clamp

pump. Keep

"HARD" J

Clamp

 

(Loosen For Step 1)

downward

(Loosen For Step 1)

Drain Tube

 

Drain Tube

(Retighten for Step 3)

 

 

(Retighten for Step 3) slope.

 

 

Route to floor drain.

...OR Route to condensate pump. Keep downward slope.

Figure 21. Furnace with Condensate Drain Trap Assembly

21

Page 21
Image 21
Nordyne G6RL 90+ Drainage Of Condensate From Furnace, Elbow Combustion Air Intake, Plumbing Vent Roof Boot Typ. Both Pipes