Nordyne G6RC 90+ G6RC & G6RD Upflow Furnaces, G6RL Downflow Furnaces, Horizontal Venting

Models: G6RD 93+ G6RC 90+ G6RL 90+

1 36
Download 36 pages 42 Kb
Page 16
Image 16
G6RC & G6RD Upflow Furnaces

G6RC & G6RD Upflow Furnaces

 

 

 

 

Inlet

Exhaust

See Vent Table 4

 

 

 

 

5/8"

 

 

 

Seal/Caulk

 

 

 

 

 

 

 

 

 

 

 

Straps or Other Suitable

 

 

around Pipe

 

 

Supports at Minimum of 5 ft. Intervals

 

at Building

Combustion

 

Coupling

 

 

90˚ Elbow

 

 

 

 

 

 

Offset with

 

 

 

 

 

 

Exhaust Pipe

 

 

 

 

 

 

for Adequate

 

 

 

 

 

 

Dimensional

 

Upward Pitch - 1/4" per Foot

 

 

12" Min.

Clearance

 

 

 

PVC or

 

Outlet Exhaust Vent

 

7"

 

 

 

First Support Placed

 

 

 

 

ABS Pipe

 

 

 

 

 

 

 

as Close to Furnace

Wall

 

 

 

 

 

Connection as Possible

 

Normal Snow Level

 

 

Exhaust Vent

 

 

 

 

 

 

 

Straight Neoprene Coupling

 

 

 

 

with 2 Hose Clamps*

 

 

 

 

 

(Optional - Not Shown)

 

 

 

 

 

G6RL Downflow Furnaces

 

 

 

 

 

 

 

See Vent Table 4

Exhaust

Inlet

5/8"

 

 

 

 

Seal/Caulk

 

 

 

 

 

 

 

 

 

 

around Pipe

 

Straps or Other Suitable

 

 

 

 

at Building

Supports at Minimum of 5 ft. Intervals

 

 

 

 

90˚ Elbow

Coupling

 

 

Combustion Air

 

 

 

 

 

 

 

 

 

 

Inlet

 

 

 

 

 

Offset with Exhaust

 

 

 

 

 

Pipe for Adequate

 

Upward Pitch - 1/4" per Foot

 

 

Dimensional

12" Min.

 

 

Clearance

 

Outlet Exhaust Vent

 

 

 

 

 

 

 

PVC or

 

 

First Support Placed

 

 

 

 

 

 

 

 

ABS Pipe

 

Wall

as Close to Furnace

 

 

 

 

 

 

 

 

 

Connection as Possible

 

 

 

 

Normal Snow Level

 

 

 

Straight Neoprene

Exhaust Vent

 

 

 

 

 

 

Coupling with

 

 

 

 

 

 

 

 

 

 

 

2 Hose Clamps

Figure 14. Horizontal Venting

*These couplings are field-supplied and can be used if the installation requires breakable connections in the piping. Note that a maximum of two couplings per pipe are allowed.

16

Page 16
Image 16
Nordyne G6RC 90+, G6RL 90+, G6RD 93+ G6RC & G6RD Upflow Furnaces, G6RL Downflow Furnaces, Horizontal Venting