Furnace | Cabinet | Nominal | Maximum | Minimum | Maximum | Minimum | Maximum |
Input | Width | Electrical | Operating | Operating | Furnace | Wire | Fuse or Circuit |
(Btuh) | (in.) | Supply | Voltage | Voltage | Amperes | Gauge | Breaker Amps* |
40,000 | 14.25 | 127 | 103 | 12.2 | 14 | 15 | |
60,000 | 14.25 | 127 | 103 | 12.2 | 14 | 15 | |
80,000 | 19.75 | 127 | 103 | 14.1 | 14 | 15 | |
100,000 | 19.75 | 127 | 103 | 14.1 | 14 | 15 | |
120,000 | 22.50 | 127 | 103 | 17.3 | 12 | 20 |
*
Thermostat | Recommended Thermostat | |
Wire | Wire Length | |
Gauge | 4 or | |
| (heating) | (cooling) |
24
22
20
18
55 ft. | 25 ft. |
90 ft. | 45 ft. |
140 ft. | 70 ft. |
225 ft. | 110 ft. |
Table 11. Electrical Data
|
|
|
|
| A/C Condensing Unit |
|
|
| ||||
|
|
|
|
| Condensing Unit |
|
|
|
| |||
|
|
|
|
|
| Control Box |
|
|
|
|
| |
|
|
|
| COM |
|
| Blower Off | 60 90 120 180 | ||||
|
|
|
|
|
|
|
| |||||
| R | R |
|
| 3 Amp |
| Timing |
|
| |||
Connect | C |
| 24 V |
| Fuse |
|
|
| TWIN | |||
|
|
|
|
|
|
| ||||||
Y |
|
|
|
|
|
|
|
|
| |||
R & W | Y |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| ||
For | G |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| Flame Signal Light |
| ||||||
Heating |
|
|
|
|
|
| ||||||
W | G |
|
|
|
|
|
| (Yellow) |
| |||
Only |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| |||
Room | W |
|
|
|
|
| Status Light |
| ||||
|
|
|
|
|
|
| ||||||
9 | 6 | 3 |
|
|
|
|
| (Red) |
| |||
Thermostat |
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
| |||||
|
| 8 | 5 | 2 |
|
|
|
|
|
|
|
|
|
| 7 | 4 | 1 |
|
|
|
|
|
|
|
|
NOTE: The "Y" |
|
|
|
|
|
|
|
|
|
|
| |
terminal on the | EAC |
|
|
|
|
|
|
|
|
|
| |
UTEC control board |
|
|
|
|
|
|
|
|
|
| ||
must be connected |
|
| Neutrals |
|
|
|
|
|
| |||
to the thermostat. | HUM |
|
|
|
|
|
|
| ||||
|
|
| HUM | M3 M2 M1 | COOL | HEAT | XFMR EAC |
| L1 | |||
FIELD WIRING |
|
|
| Unused Motor Leads |
|
|
| |||||
|
| 6 | 3 |
|
|
|
|
|
|
| ||
Low Voltage |
|
|
|
|
|
|
|
|
|
| ||
|
|
| 5 | 2 |
|
|
|
|
|
|
| |
Connections |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| 4 | 1 |
|
|
|
|
|
|
|
Figure 24. Low Voltage Field,
Four-wire Heating/Cooling Applications
2.The thermostat wires (R, W, Y, and G) are securely connected to the correct leads on the terminal strip of the circuit board.
3.The gas line service pressure does not exceed 10.0 in. water column (0.36 psig), and is not less than 4.5 in. water column (0.16 psig) for natural gas. For LP gas the line service pressure must not exceed 14 in. water column (0.51 psig), and must not be less than 11.0 in. W.C. (0.40 psig).
4.The
for location. DO NOT install a jumper wire across a switch to defeat its function. If a switch reopens on
5.The blower door is in place, closing the door switch in the line voltage circuit.
6.The gas line has been purged and all con- nections are leak tight.
Start-Up Procedure
1.Set the thermostat to the lowest setting.
2.Close the disconnect(s) to provide line volt- age to the furnace.
3.Follow the procedures given on the operat- ing instructions label attached to the furnace.
4.Set the thermostat above room tempera- ture and verify the sequence of operation. (See the SEQUENCE OF OPERATION.)
5.After the furnace has run for approximately five minutes, set the thermostat below room temperature and verify steps (9) through (11) of the SEQUENCE OF OPERATION.
Verifying and Adjusting
Firing Rate
The firing rate must be verified for each installa- tion to prevent
NOTE: The firing rate must not exceed the rate shown on the furnace rating plate. At altitudes above 2000 ft. the firing rate must be adjusted as described in the high altitude section.
26