Furnace Rating | Orifice Drill Size | |
|
| |
Plate Input (Btu/h) | Nat | LP |
|
|
|
45000 | 44 | 54 |
60000 | 45 | 55 |
72000 | 43 | 54 |
96000 | 43 | 54 |
120000 | 43 | 54 |
144000 | 43 | 54 |
Table 9. Natural and LP Gas Orifice Sizes
for Elevations between zero and
4999 ft. Above Sea Level
used in this furnace require an earth ground to operate properly. Acceptable methods for grounding are electrical wire or conduit ap- proved for electrical ground service. Do not use gas piping as an electrical ground.
NOTE: Proper line voltage polarity must be maintained in order for the control system to operate correctly. Verify that the incoming neutral line is connected to the white wire and the incoming "hot" line is connected to the black wire in the furnace junction box. These furnaces will not operate unless po- larity and ground are properly connected. See Figure 23.
!CAUTION:
Label all wires prior to disconnection when servicing controls. Wiring er- rors can cause improper and danger- ous operation. Verify proper opera- tion after servicing.
Furnace Rating | Orifice Drill Size | |
|
| |
Plate Input (Btu/h) | Nat | LP |
|
|
|
45000 | 44 | 55 |
60000 | 45 | 56 |
72000 | 43 | 55 |
96000 | 43 | 55 |
120000 | 43 | 55 |
144000 | 43 | 55 |
Table 10. Natural and LP gas Orifice Sizes for Elevations between 5000 and 10,000 ft.
Above Sea Level
nace. See Figure 24 for the proper connections for heating only
The thermostat must not be installed on an outside wall or any other location where its opera- tion may be adversely affected. Adverse affects include radiant loading from fireplaces, sunlight, or lighting fixtures, and convective loading from warm air registers or electrical appliances.
To check the heat anticipator setting either:
1.Add the current draw of the system compo- nents; or
2.Measure the current flow on the thermostat
Set the heat anticipator according to the thermo- stat manufacturer's instructions for heat antici- pator settings.
START-UP AND ADJUSTMENTS
Low Voltage Wiring
Install the thermostat per the manufacturer's instructions. The low voltage (24 volt) connec- tions from the thermostat are made at the terminal strip on the control board in the fur-
Prior to
1.The line voltage power leads are securely connected, that the polarity of the connec- tions is correct, and that the furnace is properly grounded.
Field Supplied | Field Supplied |
| |
Fused Service |
| ||
Panel Connector |
| ||
Panel |
| ||
|
|
| |
Black (Hot) | Black | Black | Black |
White (Neutral) | White | White | White |
Green or Bare |
|
|
|
(Ground) |
| Ground | Ground |
Ground |
|
Field Supplied Disconnect
Within Sight of Furnace
Field Line Voltage Wiring
Factory Line Voltage Wiring
Figure 23. Line Voltage Field Wiring