5.The vent termination for a 1-pipe installa- tion shall be a minimum of 3 ft. above any forced air inlet within 10 ft.

6.The vent termination shall be located at least 4 ft. horizontally from any electric meter, gas meter, regulator and any relief equipment. These distances apply ONLY to U.S. installations. In Canada, the Canadian Fuel Gas Code takes precedence.

7.Avoid areas where condensate drainage may cause problems by dropping on plant- ers or patios, etc. Also ensure that exhaust gases will not impinge on windows or build- ing surfaces, which may be compromised or damaged by condensation. Do not install the vent terminal such that exhaust is di- rected into window wells, stairwells, under decks or into alcoves or similar recessed areas, and do not terminate above any public walkways.

8.Select the point of wall penetration where the minimum 1/4 inch per foot of slope up can be maintained.

!CAUTION:

For optimum performance, vent fur- nace through wall which experiences the least exposure to winter winds.

Horizontal Venting

Vent and combustion air intake terminations must be as shown in Figure 19.

!WARNING:

Ensure that the combustion air vent and the exhaust vent are configured as shown in Figure 19. Improper vent termination can cause recirculation of the flue gases. This may result in fur- nace vibration. In severe cases, the furnace will cycle due to the intermit- tent contact between the flame and the flame sensor. If you note oscillations occurring, check the vent configura- tion. Make sure that the exhaust vent does not have a 90 degree termination.

Vent Configuration to

 

Provide 12" Minimum

 

height above

 

 

Snow Level.

12" Min.

 

 

 

 

19" Max.

 

Outside

Support

12" Above

Wall

 

 

Normally

 

 

Pipe

 

Expected

1/2"

Snow

Coupling

Level

Armaflex

 

 

 

Insulation or

 

 

Equivalent

 

Figure 18. Alternate Horizontal Vent

Installation

For horizontal venting, one of the following kits is recommended:

 

2" PVC

3" PVC

Through-the-Wall

9023730

9023750

Exterior Vent

Mounting Kit

 

 

Neutralizer Kit - All

9023730

9023730

Models

 

 

For Canadian installations please refer to the Canadian Installation Code (CAN/CGA-B149.1 or 2) and/or local codes.

The kit consists of two face plates and an insulating gasket to seal the exterior surface. A hole sized closely to the pipe diameter must first be cut through the wall. A short length of pipe is then cut such that it can penetrate the wall and be held in place by closely fitting standard cou- plings. The face plates are retained on both sides of the wall by the couplings, and the gasket is retained against the wall by the outer face plate. Face plates must be fastened to the wall and the outside one must be flashed as appro- priate to prevent entry of water.

When the above kits are not used the following steps are required:

1.Check the hole size cut through the exterior wall. Insure that the hole diameter is less than the diameter of the couplings to be used.

2.Extend the vent pipe through the wall ap- proximately 1" and seal the area between the wall and pipe.

19

Page 19
Image 19
Nordyne G6RC 90+, G6RL 90+, G6RD 93+ installation instructions Horizontal Venting, Alternate Horizontal Vent Installation