C.CONTROL OF DUCT OR PLENUM SATURATION

NOTE

Maximum capacity of the NHTC/NHPC humidifier can be limited through the keypad.

C.CONTROL OF DUCT OR PLENUM SATURATION

(1)NORTEC always recommends the use of a high limit humidistat set at 85% relative humidity in combination with an air-proving switch to assure air movement. Both of these controls are wired in series across the primary control terminals of the humidifiers so that should either of these conditions not be satisfied the humidifiers cannot operate.

(2)Low temperature, shallow ducts or branch ducts might require a field supplied condensate drain pan and should be accessible to service and inspection (See Figure 4.).

(3)The most effective method of ensuring controlled absorption distances is to install a modulating high limit humidistat. By controlling the down stream [after distributor(s)] humidity levels and modulating the humidifier’s output, one of the variables affecting absorption distance is now a constant. NORTEC recommends modulating high limit humidistats on all economizer systems, VAV, VVT, and systems, which are primarily cooling.

Figure 4. Condensate Drain Pan