7.CONTROLS
A.GENERAL
(1)NORTEC humidifiers all accept on/off controls for their security loop. Many NORTEC humidifiers can also accept modulating or transducer signals for control (See the features section for each specific model).
CAUTION
REGARDLESS OF SELECTING ON/OFF OR MODULATING CONTROL
METHOD, NORTEC HUMIDIFIERS MUST HAVE CLOSED CIRCUIT
ACROSS ITS ON/OFF SECURITY LOOP CONTROL TERMINAL TO
OPERATE. NORTEC HIGHLY RECOMMENDS THE USE OF A HIGH
LIMIT HUMIDISTAT AND AN AIR PROVING SWITCH IN SERIES FOR
THIS FUNCTION.
B.ON/OFF CONTROLS
(1)On/Off controls are used in all NORTEC humidifier security loops. The digital humidistat can also be used as a space humidity controller. These controls include:
(a)Air Proving Switch – duct mounted, pressure differential switch, adjustable set point from 0.07 IWC to 12.0 IWC, good for positive, negative or differential pressure applications, stops humidifier if duct air pressure is not sensed. Turns humidifier off if air handler fails.
(b)Duct Mounted Digital Humidistat – control or high limit, adjustable set point from
(c)Wall Mounted Digital Humidistat – control or high limit, adjustable set point from
(d)On/Off Controls Supplied by Others – Can be used as long as they have a dry set of contacts capable of passing a
C.MODULATING CONTROLS
(1)Modulating Controls are used to send a modulating demand signal to the NORTEC humidifier. Different models can accept different signals (see features section for each specific model) NORTEC supplied controllers send a
(a)Wall Mounted Digital Humidistat with Integrated Sensor – control or high limit, adjustable set point from
(b)Wall Mounted Digital Humidistat Without Sensor – control or high limit, adjustable set point from
(c)Duct Mounted Digital Humidistat With Sensor – This package comes with both a remote sensor and a wall mounted controller without sensor. Control or high limit, adjustable set point from