Table 11. Controls – ON/OFF

Table 11. Controls – ON/OFF

Part No.

Description

Qty

 

 

 

 

2520259

DIGITAL HUMIDISTAT WALL MOUNTED ON/OFF

Control

____

 

On/off wall mounted humidistat applicable as control humidistat or high limit

 

 

 

10% to 90% RH range with 5% non-adjustable differential.

High Limit

____

 

 

 

 

2520273

DIGITAL HUMIDISTAT DUCT MOUNTED ON/OFF PACKAGE

Control

____

 

On/off duct mounted humidistat, applicable as a control humidistat or high limit,

 

 

 

15% to 90% RH range with 4% non-adjustable differential.

High Limit

____

 

 

 

 

132-9109

PRESSURE ELECTRIC SWITCH

 

 

 

On/off, remote mounted, 3 to 20 PSIG range, factory set to 13 PSIG with 2 to

 

 

 

6 PSIG fully adjustable differential, factory set to 3 PSIG. For use with

 

 

 

pneumatic humidistat (by others).

 

 

 

 

 

 

132-9203

AIR PROVING

 

 

 

On/off duct mounted, pressure differential switch, 0.07 IWC to 12.0 IWC fully

 

 

 

adjustable operating range, good for positive, negative or differential pressure

 

 

 

applications, stops humidifier if no differential pressure is sensed.

 

 

 

 

 

 

146-9000

COUPLED CIRCUITS

 

 

 

Factory internally wired in parallel to enable control of double circuit unit from

 

 

 

one set of external controls. Applies to NHTC 150 and 200 models only.

 

 

 

 

 

 

NOTE: NORTEC NH Series humidifiers must have a closed circuit across terminals 8 and 10. NORTEC highly recommends the use of a high limit humidistat and air proving switch in series for this function.

Table 12. Modulating Control By NORTEC

Part No.

Description

Qty

 

 

 

 

2520266

DIGITAL WALL CONTROLLER WITH DUCT SENSOR PACKAGE

Control

____

 

This is a digital LCD setpoint controller with a duct mounted humidity sensor

 

 

 

used for modulating high limit or control.

High Limit

____

 

 

 

 

2520261

DIGITAL WALL CONTROLLER WITHOUT INTEGRAL SENSOR

Control

____

 

This is a digital LCD setpoint controller to be used with one or all of the

 

 

 

following remote sensors: remote wall sensor, remote duct sensor and outdoor

High Limit

____

 

duct mounted temperature sensor.

 

 

 

 

 

 

1510142

DIGITAL WALL CONTROLLER WITH INTEGRAL SENSOR

Control

____

 

This is a digital LCD setpoint controller with a wall mounted humidity sensor

 

 

 

used for humidity control in the space.

High Limit

____

 

 

 

 

2520263

OUTDOOR DUCT MOUNT TEMPERATURE SET BACK

 

 

 

This sensor can be mounted directly onto the fresh air intake of the ventilation

 

 

 

duct. The humidistat controller reads the outdoor temperature and resets the

 

 

 

humidity control setpoint to prevent condensation in windows or building

 

 

 

structures. Use with modulating controllers above.

 

 

 

 

 

 

1509857

REMOTE DUCT SENSOR

 

 

 

This humidity sensor can be mounted directly onto the return ventilation as the

 

 

 

main controlling sensor. It can also be used as a supply high limit sensor. It

 

 

 

must be used in conjunction with any other controller for remote sensing.

 

 

 

 

 

 

1509858

REMOTE WALL SENSOR

 

 

 

This humidity sensor can be mounted on a wall as the main controlling sensor.

 

 

 

It must be used in conjunction with any other controller for remote sensing.

 

 

 

 

 

 

10-30

Page 112 2008-10-01

Page 120
Image 120
Nortec NHPC, NHTC manual 10-30, Controls – ON/OFF, Modulating Control By NORTEC, Page 112