Figure 3. Steam Distributor Location

Table 9. Typical Absorption Distances, Single Distributor, 100 lbs/hr Humidifier

FPM

°F

 

°C

% RH

FT

 

CM

Typical System

 

 

 

 

 

 

 

 

(V)

 

(T)

(H)

 

(D)

 

 

 

 

 

 

 

 

 

 

 

 

500

70

 

21

30

3.0

 

91

Air handler before coils

 

 

 

 

 

 

 

 

 

500

55

 

13

80

4.5

 

137

Air handler after cooling

 

 

 

 

 

 

 

 

 

900

70

 

21

30

3.5

 

107

Supply air duct, on cool, no heat

 

 

 

 

 

 

 

 

 

900

55

 

13

70

6.0

 

183

Supply air duct, on cool

 

 

 

 

 

 

 

 

 

1000

55

 

13

90

8.0

 

244

Supply air duct, on cool with high humidity

 

 

 

 

 

 

 

 

 

1000

110

 

43

10

2.5

 

76

Supply air duct, on heating with low humidity

 

 

 

 

 

 

 

 

 

1000

70

 

21

45

4.0

 

123

Return air duct conditions

 

 

 

 

 

 

 

 

 

2000

55

 

13

45

10.0

 

305

Supply air duct higher pressure system

 

 

 

 

 

 

 

 

 

5000

140

 

60

10

2.0

 

61

After operating heating coil

 

 

 

 

 

 

 

(V) = Velocity at distributor location

(T) = Temperature at distributor location

(D) = Absorption distance (visible steam)

(H) = Humidity level after steam is absorbed

NOTE: This chart is for reference only; multiple distributors can reduce absorption distances.