(7)Vertical drop of the drip station should be 1.5 times the diameter of the steam main but no less then 12".

(8)Install the P trap at the botom of the drip station. The P trap height is to be a minimum of 6 inches or 2 “ greater than the static pressure in the duct.

(9)All distributors must be individually trapped.