Nortel Networks 8600 manual Using Two DC Power Sources for Power Redundancy, 2-14, Procedure

Models: 8600

1 62
Download 62 pages 39.02 Kb
Page 30
Image 30
48VDC CLASS 2 OR LIMITED PWR SOUR

Installing and Connecting the Hardware

2. Dress the wires under the 8600 chassis to the left behind the support foot.

AC

INPUT

AC

T5A

250V

–48V

RTN

A

B

A B

48VDC CLASS 2 OR LIMITED PWR SOUR

-48V B A

F RTN G B A

INPUT

48VDC

97-15446-01

3.Power the HotWire 8600 DSLAM chassis.

4.Make sure the DC PWR A LED on the front panel is ON (green).

Using Two DC Power Sources for Power Redundancy

"Procedure

To supply two dc power sources to the 8600 chassis for power redundancy:

Using Two DC Power Sources for Power Redundancy Make sure that the dc power source wires are not powered (i.e., the circuit breakers are open).

2-14 The ends power source wires (14 AWG ± 18 AWG solid or stranded wire) must be stripped of insulation to about 1/3-inch in length before plugging the wires into the appropriate terminal on the ±48V input terminal block.

1.Insert the following wires in the appropriate terminal and securely fasten each wire by tightening the screw directly above it. The insulation should be fully within the terminal block and no bare wire should be exposed outside of the block.

NOTE:

You should clearly label these power source wires as ±48V and RTN respectively.

2-14

October 1997

8600-A2-GN20-20

Page 30
Image 30
Nortel Networks 8600 Using Two DC Power Sources for Power Redundancy, 2-14, Procedure, 48VDC CLASS 2 OR LIMITED PWR SOUR