VENTING - RESTRICTOR PLACEMENT

Optima 45 - 3

13

VENTING - RESTRICTOR PLACEMENT

RESTRICTOR PLACEMENT FOR SIDEWALL VENTED APPLICATIONS ONLY

WARNING: These restrictors are only to be installed in the vent system if the vent exceeds 10’ in vertical height. See below which restrictor to use.

Installing them under any other circumstances may cause hazardous venting conditions and may result in personal injury, property damage or death.

NOT FOR USE IN VERTICALLY VENTED APPLICATIONS

Restrictor Number #1

Restrictor Number #2

Sidewall Venting - Above

Sidewall Venting - Above

Ten Feet (10’)

Eighteen Feet (18’)

 

 

 

NOTE: Vent restrictors are designed to reduce vertical stack action for vent terminations which will reduce the velocity of incoming combustion air and not adversely affect the standing pilot or the efficiency of the appliance.

Simpson Dura-Vent

 

Archgard System

With Simpson Dura-Vent,

 

In the Archgard system, the

locate the restrictor in the exhaust

 

restrictors are placed on the

section fitting into the formed lip.

 

exhaust outlet on the appliance.

 

 

 

Simpson Dura-Vent

 

Archgard System

 

 

 

Page 13
Image 13
Optima Company 45 - 3 manual Venting - Restrictor Placement, Optima, Not For Use In Vertically Vented Applications