VENTING CHART
The appliance will not function without being connected to a proper venting system. This appliance may only use direct vent system supplied by Archgard, or Simpson Dura- Vent direct vent systems with Archgard
7.93 M
7.32 M
V | 6.71 M |
E |
|
R6.10 M
T
I5.49 M
C
A4.88 M
L
4.27 M
H
E3.66 M
I
G3.05 M
H
T2.44 M
1.83 M
1.22M
610 mm
No restrictors are to be used in vertical vent installations.
Sidewall installation only
| Note: No Installations are |
Sidewall | permitted outside of this |
range. | |
installation only |
|
Note: See instructions on page
13 for restrictor placement.
610 | 1.22 | 1.83 | 2.44 | 3.05 | 3.66 | Meters |
mm |
Feet
•A minimum of 3’ (914 mm) of vertical vent to center of elbow is required for a maximum horizontal run of 3’ (914 mm).
•Chart is for one 90° bend, with ¼” (7 mm) vertical raise minimum per foot of horizontal length.
•For each additional 90° or two 45°, add one foot of vertical height.
•Maximum three 90º bends, or equivalent.
•Minimum 2 ft (610 mm) straight length between bends.
VENTING ABOVE ROOF OF THE HOUSE USING A VERTICAL TERMINATION
Use Simpson
applications (through the roof).
Please strictly follow the venting instructions for optimum performance from the appliance and to avoid sooting and/or service calls.