CHECKING INLET AND OUTLET GAS PRESSURE
1.Remove the control panel.
2.The pressure test taps are located on the valve. The taps are located on the gas valve front face. The inlet is marked ‘IN’ and the outlet is marked ‘OUT’. (See Fig.1)
3.Loosen the set screw inside the tap with a ⅛” (3 mm) wide flat screwdriver.
4.Connect a ¼” (6 mm) rubber tube to the tap post and a manometer.
5.Verify the readings obtained are within specs (as shown on the appliance rating plate)
6.Be sure to tighten the set screw inside the tap after you are finish taking pressure readings.
7.Check for leaks.
OUT (manifold) |
| IN (inlet) |
|
|
|
|
|
|
Fig. 1
CHECKING AND ADJUSTING PILOT
CONVERTIBLE PILOT ORIFICE
7/16”
(11 mm)
WRENCH
(HERE)