VENTING - HORIZONTALLY USING SIMPSON DURA-VENT DIRECT VENT SYSTEMS

INSTALLATION PROCEDURES FOR SIMPSON DURA-VENT DIRECT VENT SYSTEM

5.Mark the wall with an 11” (279 mm) x 10” (254 mm) hole. See termination framing on page 22. The center of the hole should line up with the centerline of the horizontal pipe. Cut and frame the 11” (279 mm) x 10” (254 mm) hole in the ex- terior wall where the vent will be terminated. If the wall be- ing penetrated is constructed of non-combustible material, (I.E. a masonry block, or concrete) a hole with zero clear- ance is acceptable. NOTE: The horizontal run of vent must be level, or have a ¼” (6 mm) rise for every 12” (305 mm) of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fire. ALSO: The location of the

horizontal vent termination on an exterior wall must meet

 

Fig. 1

local and national building codes, and must not be blocked

 

 

or obstructed. For Allowable Termination Locations see

 

 

Fig. 2

 

page 11 in this manual.

 

 

 

6.Position the Horizontal Vent Termination in the center of the square hole (arrow on the vent cap should be facing UP), and run a bead of non-hardening sealant around the outside edges of the termination, so as to make a seal between the termination and the wall. Finish attaching the termination cap to the wall with the four wood screws provided with the termination cap. NOTE: The four wood screws provided should be replaced with the appropriate fasteners for stucco, brick, concrete or other types of siding. For buildings with VINYL SIDING, a Vinyl Siding Standoff should be in- stalled between the vent cap and the exterior wall. Attach the Vinyl Siding Standoff to the Horizontal Termination Cap by bolting the flat portion of the Vinyl Siding Standoff (Fig.1) so that an air space will exist between the wall and the Vent Termination.

7.Locate and slide the Wall Thimble Cover over the vent pipe.

8. Slide the appliance and vent assembly towards the wall,

 

Fig. 3

carefully inserting the vent pipe into the vent cap assembly.

 

It is important that the vent pipe extend into the vent cap

 

sufficient distance so as to result in a minimum pipe overlap

 

of 1 ¼” (31 mm). Secure the connection between the vent

 

pipe and the vent cap by attaching the two sheet metal

 

strips extending from the vent cap assembly into the outer

 

all of the vent pipe. Use the two sheet metal screws pro-

 

vided to connect the strips to the pipe section. Bend any re-

 

maining portion of the sheet metal strip back towards the

 

vent cap, so it will be concealed by the Wall Thimble Cover.

 

(Fig. 2)

 

9. Slide the Wall Thimble Cover up to the wall surface and at-

 

tach to the wall with wood screws. (Fig. 3)

 