FLEXNet DC Measurements

The FLEXNet DC can measure and record:

 

 

 

• Volts for one battery bank*

 

 

 

• Amps**

For

each

 

• KiloWatts

 

 

channel

 

 

• kWhrs removed from the batteries

 

 

 

 

 

• kWhrs returned to the batteries

 

 

 

• Amp hours removed from the batteries

 

 

 

• Amp hours returned to the batteries

 

 

 

• Battery bank state-of-charge

 

 

 

• Lifetime kiloamp hours removed from the batteries***

 

 

• Days since charge parameters last met

 

 

 

• Lowest battery state-of-charge reached

 

 

 

• Minimum battery voltage***

For

 

 

• Maximum battery voltage***

 

 

each

 

 

• Maximum amp charged***

 

 

amps

 

• Maximum amp discharged***

 

 

channel

• Maximum kWhrs charged***

 

• Maximum kWhrs discharged***

* Battery volt input: 0-80 VDC in .1 volt resolution

** 2000 amp DC span (+/- 1000 amps DC—net amps are charging, net amps are discharging), .1 amp resolution

*** The user can manually reset these data. At any given time, the values displayed are the most recent since the values were last displayed