Logged Data*

The previous 128 days of data are accessible with the MATE. The data is logged each night at midnight. Be sure the MATE’s clock is set to the correct local time (refer to your MATE manual).

* Data Logging

User Adjustable Set Points

Battery charge factor (65-100%) [see page 29]

Battery bank capacity 0-10000 amp hours

Shunt A, B, C—enabled or disabled

Absorb volts (0-80.0 volts, the maximum voltage the battery can absorb)

Return amps (0-500.0A, the maximum current amperage going into the battery)

Parameters met timer (0-240 minutes, the amount of time allowed to recharge)

AUX Relay Set Points

Manual-On, Auto, Manual-Off—allows the user to turn the Aux Relay on and of like a manualf switch or to set it to Auto and have it function when certain conditions are met

Volts HI—when user determined high voltage value is met, the Aux activates

Volts LO—the Aux activates when a low voltage value is met

SOC (State-of-Charge) HI—a high state-of-charge activates the Aux

SOC (State-of-Charge) LO—a low state-of-charge activates the Aux

HI Delay—the user can adjust the high set point delay time (in minutes)

LO Delay—the user can adjust the low set point delay time (in minutes)

AUX-INVERT LOGIC—the invert logic function can be activated with a YES or NO command (see page 16)