Panasonic CU-2E18NBU service manual Installation Instruction, Select The Best Location

Models: CU-2E18NBU

1 57
Download 57 pages 29.38 Kb
Page 16
Image 16
10. Installation Instruction

10. Installation Instruction

10.1 Select The Best Location

10.1.1Outdoor Unit

šIf an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed.

šThere should not be any animal or plant which could be affected by hot air discharged.

šKeep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.

šDo not place any obstacles which may cause a short circuit of the discharged air.

šRecommended installation height for outdoor unit should be above the seasonal snow level.

Refrigerant piping size

Outdoor Unit

 

CU-2E18***

 

 

Liquid - side

ø1/4” thickness 1/32”

 

 

Gas - side

ø3/8” thickness 1/32”

 

 

 

 

 

 

Outdoor Unit

 

CU-2E18***

 

 

Min. total piping length for additional gas

65.6 ft

šIf total piping length of all indoor units exceeds the minimum length listed above, additionally charge with 0.2 oz of refrigerant (R410A) for each additional meter of piping.

Allowable piping length

Outdoor Unit

 

CU-2E18***

 

 

 

 

Allowable piping length of each indoor unit (min. ~ max.)

 

9.8 ft ~ 82 ft

 

 

 

 

Allowable total piping length of all indoor unit

 

164 ft or less

 

 

 

 

Height difference between indoor and outdoor unit

Outdoor unit located on upper side

 

49.2 ft or less

 

 

 

Outdoor unit located otherwise

 

24.6 ft or less

 

 

 

 

 

 

Height difference between indoor unit

Outdoor unit located on upper side

 

24.6 ft or less

 

 

 

Outdoor unit located otherwise

 

49.2 ft or less

 

 

 

 

 

 

16

Page 16
Image 16