11.1 Cooling Operation

11.1.1Outdoor fan control

šWhen cooling operation is enabled, based on outdoor ambient temperature, fan motor control will be adjusted according to figure below:

11.1.2Annual Cooling control

šThis control is to enable cooling operation when outdoor ambient temperature is low.

šControl start conditions:

o Cooling operation is activated with compressor ON. o Outdoor ambient temperature is less than 59°F

šControl contents:

o When the above conditions are fulfilled, based on outdoor pipe temperature, the outdoor fan motor will operate according to figure below:

šTo improve the judgment accuracy during annual cooling control, outdoor ambient temperature sampling for 2 minutes will be activated every 35 minutes under designated fan speed.

šControl stop conditions:

o When either one of the start conditions are not complied.