13. Protection Control

13. Protection Control

13.1 Freeze Prevention control (Cool)

šWhen received freeze prevention signal from indoor unit, the compressor frequency changes according to indoor heat exchanger temperature.

šWhen indoor unit request capability OFF due to freeze condition , immediately the capability supply to targeted indoor unit stops.

13.2 Dew Prevention control (Cool)

šWhen received dew prevention signal from indoor unit, the compressor frequency changes according to indoor intake temperature and indoor heat exchanger temperature.

13.3 Electronic Parts Temperature Rise Protection 1 (Cool)

šThis control prevents electronic parts temperature rise during cooling overload condition.

šStart conditions:

o Outdoor ambient temperature is at protection region as shown in figure below:

oOutdoor unit total current is above 5.5A

šControl content

oOutdoor fan speed is adjusted accordingly.

šControl stop condition

oWhen outdoor ambient temperature is back to normal region.

šDuring this control, outdoor fan speed does not reduce for Quiet operation.

13.4 Electronic Parts Temperature Rise Protection 2 (Cool)

šThis control prevents electronic parts temperature rise during cooling/dry operation.

šStart conditions:

o Total current is at protection region as shown in figure below:

šControl content

o Outdoor fan speed is adjusted accordingly.

šControl stop conditions

o When total current is back to normal region.

šDuring this control, outdoor fan speed does not reduce for Quiet operation.