Panasonic CS-KS18NKU, CU-KS18NKU service manual Refrigerant Tubing, Use of the Flaring Method, Fig

Models: CS-KS18NKU CU-KS18NKU

1 122
Download 122 pages 36.27 Kb
Page 113
Image 113
5. Refrigerant Tubing

5. Refrigerant Tubing

5-1. Use of the Flaring Method

Many of the conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units. In this method, the copper tubes are flared at each end and connected with flare nuts.

5-2. Flaring Procedure with a Flare Tool

(1)Cut the copper tube to the required length with a tube cutter. It is recommended to cut approx. 12" to 20" (30 to 50 cm) longer than the tubing length you estimate.

(2)Remove burrs at the end of the copper tube with a tube reamer or file. This process is important and should be done carefully to make a good flare.

(Fig. 47)

NOTE

Deburring

Before

After

 

 

Fig. 47

Copper tubing

Reamer

When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube. (Fig. 48)

(3)Remove the flare nut from the unit and be sure to mount it on the copper tube.

(4)Make a flare at the end of copper tube with a flare tool.* (Figs. 49a and 49b)

(*Use “RIDGID” or equivalent.)

If the special R410A flare tool is used:

0 to 0.0196" (0 to 0.5 mm)

Fig. 48

If the previous flare tool (clutch-type) is used:

5-1. Use of the Flaring Method5-2. Flaring Procedure with a Flare Tool5-3. Caution before Connecting Tubes Tightly 0.0472" (1.2 mm)

Adjust so that the amount of tube protrusion is as shown in the figure.

NOTE

A good flare should have the following characteristics:

inside surface is glossy and smooth.

edge is smooth.

tapered sides are of uniform length.

5-3. Caution before Connecting Tubes Tightly

a)Be sure to apply a sealing cap or water-proof tape to prevent dust or water from getting into the tubes before they are used.

b)Be sure to apply refrigerant lubricant to the match- ing surfaces of the flare and union before connect- ing them together. This is effective for reducing gas leaks. (Fig. 50)

c)For proper connection, align the union tube and flare tube straight with each other, then screw in the flare nut lightly at first to obtain a smooth match. (Fig. 51)

Fig. 49a

Flare nut

Copper Fig. 49a tubing

Flare tool

Fig. 49b

Apply refrigerant lubricant here and here

Fig. 50

Union

Flare nut

Fig. 51

21

Page 113
Image 113
Panasonic CS-KS18NKU, CU-KS18NKU Refrigerant Tubing, Use of the Flaring Method, Flaring Procedure with a Flare Tool, Fig