Panasonic CU-KS18NKU, CS-KS18NKU service manual Continued from the previous page A

Models: CS-KS18NKU CU-KS18NKU

1 122
Download 122 pages 36.27 Kb
Page 52
Image 52
( Continued from the previous page A. )

( Continued from the previous page A. )

( Continued from the previous page B. )

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

Yes

 

 

Is the voltage of about DC22V to

 

 

 

 

 

24V given between the terminals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 and 3 on the indoor unit terminal strip

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Serial Communication Line) ?

 

 

 

 

 

 

 

 

 

 

 

 

 

(Fig. 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

Defect or connection error

 

 

 

 

Defect in the indoor unit

 

in the inter-unit cable

 

 

 

 

 

 

P.C. board

 

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

1. Turn OFF the power and wait until the power lamp (LED)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of the outdoor unit controller is turned OFF.

 

 

 

 

1

2

3

4

5

6

 

2. Short-circuit between the terminals 2 and 3 on the outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

unit terminal strip.

(Fig. 3)

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Turn ON the power and operate the system using the remote controller or the operation button on the indoor unit.

2.Perform the self-diagnosis five seconds after the operation start.

What is the latest self-diagnosis result ?

Condition: E01

Condition: E12

1 2 3

Indoor Unit

Fig. 3

Defect in the outdoor unit

P.C. board.

1.Turn off the power and wait until the power lamp (LED) of the outdoor unit controller is turned OFF.

2.Remove the short-circuit between the terminals 2 and 3 on the outdoor unit terminal strip.

3.Disconnect the cable from the terminal 3 on the indoor unit

terminal strip.(Fig. 4)

Short-circuit between the terminals 2 and 3 on the indoor unit

terminal board.

(Fig. 5)

 

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

 

1

2

3

 

4

5

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Unit

 

 

 

 

 

 

1

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 4

 

 

 

 

 

 

 

 

 

 

 

Fig. 5

 

 

 

 

 

1.Turn ON the power and operate the system using the remote controller or the operation button on the indoor unit.

2.Perform the self-diagnosis five seconds after the operation start.

Condition: E12

What is the latest self-diagnosis result ?Defect or connection error in the inter-unit cable

Condition: E01

Defect in the indoor unit

P.C. board

52

Page 52
Image 52
Panasonic CU-KS18NKU, CS-KS18NKU service manual Continued from the previous page A