Panasonic CS-KS18NKU Air Purging with a Vacuum Pump for Test Run, pin inside, Table, Fig

Models: CS-KS18NKU CU-KS18NKU

1 122
Download 122 pages 36.27 Kb
Page 115
Image 115
6. Air Purging

6. Air Purging

Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. Therefore, they must be purged completely.

pressure in the system rises

operating current rises

cooling (or heating) efficiency drops

moisture in the air may freeze and block capillary tubing

water may lead to corrosion of parts in the refrigerant system

Air Purging with a Vacuum Pump (for Test Run)

(1)Check that each tube (both narrow and wide tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage.

(2)Using an adjustable wrench or box wrench, remove the valve caps from the service valve on both nar- row and wide tubes.

(3)Connect a vacuum pump and a manifold valve (with pressure gauges) to the service port on the wide tube service valve. (Fig. 57)

CAUTION

The service port on the wide tube

service valve uses a Schrader core

 

 

 

valve to access the refrigerant sys-

 

tem. The valve core is similar to

 

those used in automobile tires.

 

Therefore, be sure to use a vacuum

 

hose connector which has a push-

 

pin inside.

CAUTION Be sure to use a manifold valve for air purging. If it is not avail-

able, use a stop valve (field sup- ply) for this purpose. The “Hi” knob of the manifold valve must always be kept closed.

(4)With the “Lo” knob of the manifold valve open, run the vacuum pump. The operation time for the vacu- um pump varies with tubing length and the capacity of the pump. The following table shows the amount of time for evacuation:

Table 7

Required time for evacuation when 100 liter/h vacuum pump is used

If tubing length is

If tubing length is

less than 33 ft. (10 m)

more than 33 ft. (10 m)

 

 

10 min. or more

15 min. or more

 

 

Indoor unit

Outdoor unit

Manifold valve Air Purging with a Vacuum Pump (for Test Run) (Exclusively for R410A)

Pressure

Lo

Hi

gauge

 

 

Charging hose (Exclusively for R410A)

tem. The valve core is similar tothose used in automobile tires.pin inside.Manual backgroundManual background Vacuum pump adapter (Exclusively for R410A) (with reverse flow prevention)

Vacuum pump

Fig. 57

NOTE

To prevent other refrigerants from being mistakenly charged to units which use R410A, the size of the charge port on the service valve is different from the one for other refrigerant types. For servicing such as recharging, the specified charging hose, manifold and vacuum pump adapter (with reverse flow prevention) for R410A must be used.

NOTE

The required time in Table 7 is calculated based on the assumption that the ideal (or target) vacuum condition is around 10 mmHg abs.

23

Page 115
Image 115
Panasonic CS-KS18NKU Air Purging with a Vacuum Pump for Test Run, tem. The valve core is similar to, pin inside, Fig