Pentax MMK-AP0071H Drain Piping Work, Piping and Insulation, Pipe and Drain hose formation

Models: MMK-AP0071H MMK-AP0121H MMK-AP0181H

1 181
Download 181 pages 36.37 Kb
Page 11
Image 11
4 DRAIN PIPING WORK

4 DRAIN PIPING WORK

Piping and Insulation CAUTION

Install the drain pipe in accordance with the Installation Manual so that the water is drained completely, and insulate the pipes so that no condensation forms them.

Improper pipe installation could result in water leaking indoors on furniture, etc.

REQUIREMENT

Insulate indoor drain pipes completely.

Insulate the connection with the indoor unit. Incomplete insulation could result in condensation forming.

Make sure that the drain pipe slopes downwards at a rate of 1/100 or more, do not route the drain pipe over another pipe, and do not create a trap.

These can all cause unusual sounds.

Do not apply undue force to the drain pipe connection.

NG

Do not let the drain pipe slope upwards.

Do not leave the end of the drain hose in water. Pipe and Drain hose formation

NG

Do not leave any undulations in the drain pipe.

NG

Piping and Insulation

Arrange for the following materials on site for the pipe installation and insulation work.

Piping

Hard polyvinyl chloride pipe :nominal dia. (inner dia.) ; Ø20mm

 

 

Heat insulator

Vesicant polyethylene : Thickness ; 10mm

 

 

When extending the drain hose, make the connection as shown in the figure at right.

REQUIREMENT

Using adhesive agent for vinyl chloride, connect the hard vinyl chloride pipes certainly so that water does not leak.

It requires several times to dry and harden the adhesive agent. (Refer to Guide Manual of the adhesive agent.) In this time, be sure not to apply force to the connecting section with the drain pipes.

Because the drain is a gravity drain, the pipes outside of the unit must have a downward slope.

Once the piping work is complete, pour water in the drain pan and make sure that the water drains completely.

Hard polyvinyl chloride pipe

Heat insulator

Drain pan

Drain hose

Adhesion for hard polyvinyl chloride pipe used

Indoor

Outdoor side

side

 

Pipe hole

(Grading downward to outdoor side)

Tape

Pipe and Drain hose formation

The drain pipe can be routed out of the rear, left, or right side of the unit.

When routing the drain pipe out the left or right side, align the pipe and drain hose as shown in the figure at right.

Make sure that the hose does not stick out the rear of the unit.

Pipe (Liquid side)

Installation of remote controller (Sold separately) Pipe (Gas side)

Communication

Lower cabinet

wires for control

Drain hose

Installation of remote controller (Sold separately)

For installation of the wired remote controller, follow the Installation Manual attached with the remote controller. For installation of the wireless remote controller, follow to the Installation Manual attached to the remote controller.

Do not put the woreless remote controller on the place where is exposed to direct sunlight or near a stove, etc.

Operate the remote controller, check the indoor unit surely receives the signal, and then install the remote controller. (Wireless type)

Install the remote controller 1m apart from the devices such as TV or stereo. (Image may be disturbed or noise may be output.) (Wireless type)

8

Page 11
Image 11
Pentax MMK-AP0071H, MMK-AP0121H Drain Piping Work, Piping and Insulation, Pipe and Drain hose formation, Requirement