Pentax MMK-AP0071H, MMK-AP0121H, MMK-AP0181H Test Run, In case of wireless remote controller

Models: MMK-AP0071H MMK-AP0121H MMK-AP0181H

1 181
Download 181 pages 36.37 Kb
Page 20
Image 20
8 TEST RUN

8 TEST RUN

In case of wireless remote controller

Procedure

Description

 

 

1

Remove a small screw which fixes the nameplate of the receiver unit.

Remove the nameplate of the sensor section by inserting a minus screwdriver, etc into the notch at the bottom

 

of the plate, and set the Dip switch to [TEST RUN ON].

Execute a test operation with In case of wireless remote controller button on the wireless remote controller.

2

 

,

 

, and

LED flash during test operation.

 

 

 

 

• Under status of [TEST RUN ON], the temperature adjustment from the wireless remote controller is invalid.

 

 

Do not use this method in the operation other than test operation because the equipment is damaged.

 

 

 

 

 

3

Use either COOL or HEAT operation mode for a test operation.

* The outdoor unit does not operate approx. 3 minutes after power-ON and operation stop.

 

 

 

 

 

4

After the test operation finished, stop the air conditioner from the wireless remote controller, and return Dip

switch of the receiver section as before.

 

 

(A 60-minutes timer clearing function is attached to the receiver section in order to prevent a continuous test

 

operation.)

 

Receiver unit

Spacer

M4 × 25 screw (2 pieces)

Notch Nameplate

Small screw

17

Page 20
Image 20
Pentax MMK-AP0071H, MMK-AP0121H, MMK-AP0181H installation manual Test Run, In case of wireless remote controller