Accessory parts and Parts to be procured locally
Accessory parts
Part name Q’ty | Shape | Usage | ||
Installation | 1 | This | (Be sure to hand over to customers) | |
Manual | manual | |||
|
| |||
Heat | 2 |
| For heat insulation of pipe | |
insulating pipe |
| connecting section | ||
|
| |||
Wood screw | 12 |
| For attach the installation plate | |
M4 × 35L |
| |||
|
|
| ||
Installation | 1 |
| Used install indoor unit wall unit | |
plate |
| |||
|
|
|
Part name
Installation pattern
Screw cap
Banding band
Q’ty
1
4
4
Shape | Usage |
—For confirmation of piping hole and indoor unit position
Cover on fixing screw at side plate
Used to fix attached pipe heat insulating material
Refrigerant piping
•Piping material used for the conventional refrigerant cannot be used.
•Use copper pipe with 0.8 mm or more thickness for Ø6.4, Ø9.5, Ø12.7.
Use copper pipe with 1.0 mm or more thickness for Ø15.9.
•Flare nut and flare works are also different from those of the conventional refrigerant. Take out the flare nut attached to the indoor unit of the air conditioner, and use it.
<Separate sold parts>
Part name | Q’ty | Shape | Usage |
Standard wired | 1 |
| Model |
remote controller |
| ||
|
|
Parts to be procured locally
Connecting pipe (Liquid side)
(6.4mm (diam.), Nominal (diam.) 1/4” thick 0.8mm)
(9.5mm (diam.), Nominal (diam.) 3/8” thick 0.8mm)
Connecting pipe (Gas side)
(9.5mm (diam.), Nominal (diam.) 3/8” thick 0.8mm)
(12.7mm (diam.), Nominal (diam.) 1/2” thick 0.8mm)
(15.9mm (diam.), Nominal (diam.) 5/8” thick 1.0mm)
Power supply cord
Cable