Check code

 

Wireless remote controller

 

 

 

 

 

 

 

 

 

 

 

Main

 

Outdoor 7-segment display

AI-NET central

Sensor block display

Check code name

Judging device

remote

 

 

 

 

of receiving unit

 

 

controller

 

 

 

control display

 

 

 

 

 

 

display

 

 

Auxiliary code

 

Operation Timer Ready

Flash

 

 

F01

 

0F

¤

¤

z

ALT

Indoor TCJ sensor error

Indoor

 

 

F02

 

0d

¤

¤

z

ALT

Indoor TC2 sensor error

Indoor

 

 

F03

 

93

¤

¤

z

ALT

Indoor TC1 sensor error

Indoor

 

 

F04

F04

 

19

¤

¤

{

ALT

TD1 sensor error

I/F

 

 

F05

F05

 

A1

¤

¤

{

ALT

TD2 sensor error

I/F

 

 

 

 

 

 

 

 

 

F06

F06

 

18

¤

¤

{

ALT

TE1 sensor error

I/F

 

 

F07

F07

 

18

¤

¤

{

ALT

TL sensor error

I/F

 

 

F08

F08

 

1b

¤

¤

{

ALT

TO sensor error

I/F

 

 

 

 

 

 

 

 

 

 

F10

 

OC

¤

¤

z

ALT

Indoor TA sensor error

Indoor

 

 

F12

F12

 

A2

¤

¤

{

ALT

TS1 sensor error

I/F

 

 

F13

F13

 

01: Comp. 1 side

43

¤

¤

{

ALT

TH sensor error

IPDU

 

 

02: Comp. 2 side

F15

F15

 

18

¤

¤

{

ALT

Outdoor temp. sensor miscabling (TE, TL)

I/F

 

 

F16

F16

 

43

¤

¤

{

ALT

Outdoor pressure sensor miscabling (Pd, Ps)

I/F

 

 

 

 

 

 

 

 

 

F23

F23

 

43

¤

¤

{

ALT

Ps sensor error

I/F

 

 

F24

F24

 

43

¤

¤

{

ALT

Pd sensor error

I/F

 

 

F29

 

12

¤

¤

z

SIM

Indoor other error

Indoor

 

 

 

 

 

 

 

 

 

 

F31

F31

 

1C

¤

¤

{

SIM

Indoor EEPROM error

I/F

 

 

H01

H01

 

01: Comp. 1 side

IF

z

¤

z

 

Compressor break down

IPDU

 

 

 

02: Comp. 2 side

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H02

H02

 

01: Comp. 1 side

1d

z

¤

z

 

Magnet switch error

MG-SW

 

 

 

 

Overcurrent relay operation

Overcurrent relay

 

02: Comp. 2 side

 

 

 

 

 

 

Compressor trouble (lock)

IPDU

 

 

 

 

 

 

 

 

 

H03

H03

 

01: Comp. 1 side

17

z

¤

z

 

Current detect circuit system error

IPDU

 

 

 

02: Comp. 2 side

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H04

H04

 

44

z

¤

z

 

Comp 1 case thermo operation

I/F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H06

H06

 

20

z

¤

z

 

Low pressure protective operation

I/F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H07

H07

 

d7

z

¤

z

 

Oil level down detective protection

I/F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01: TK1 sensor error

d4

 

¤

 

 

 

 

 

 

 

 

 

 

 

 

H08

H08

 

02: TK2 sensor error

z

z

 

Oil level detective temp sensor error

I/F

 

 

 

03: TK3 sensor error

 

 

 

 

 

 

 

 

 

 

 

 

04: TK4 sensor error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H14

H14

 

44

z

¤

z

 

Comp 2 case thermo operation

I/F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01: TK1 oil circuit system error

 

 

¤

 

 

Oil level detective circuit error

I/F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H16

H16

 

02: TK2 oil circuit system error

d7

z

z

 

 

 

Magnet switch error

MG-SW

 

03: TK3 oil circuit system error

 

 

 

 

 

 

Overcurrent relay operation

Overcurrent relay

 

 

 

04: TK4 oil circuit system error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L03

 

96

¤

z

¤

SIM

Indoor center unit duplicated

Indoor

 

 

L04

L04

 

96

¤

{

¤

SIM

Outdoor line address duplicated

I/F

 

 

L05

 

96

¤

z

¤

SIM

Duplicated indoor units with priority

I/F

 

 

(Displayed in indoor unit with priority)

 

 

 

 

 

 

 

 

 

 

 

 

L06

L06

 

No. of indoor units with priority

96

¤

z

¤

SIM

Duplicated indoor units with priority

I/F

 

 

(Displayed in unit other than indoor unit with

 

 

 

 

 

 

 

priority)

 

 

 

 

 

 

 

 

 

 

 

L07

 

99

¤

z

¤

SIM

Group line in individual indoor unit

Indoor

 

 

 

 

 

 

 

 

 

L08

L08

 

99

¤

z

¤

SIM

Indoor group/Address unset

Indoor, I/F

 

 

L09

 

46

¤

z

¤

SIM

Indoor capacity unset

Indoor

 

 

L10

L10

 

88

¤

{

¤

SIM

Outdoor capacity unset

I/F

 

 

 

 

 

 

 

 

 

L20

L20

 

98

¤

{

¤

SIM

Duplicated central control addresses

AI-NET, Indoor

 

 

 

L28

L28

 

46

¤

{

¤

SIM

Over No. of connected outdoor units

I/F

 

 

 

 

 

01: IPDU1 error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02: IPDU2 error

 

 

 

 

 

 

 

L29

 

 

03: IPDU3 error

CF

¤

{

¤

SIM

No. of IPDU error

I/F

 

 

L29

 

04: Fan IPDU error

 

 

 

 

05: IPDU1 + Fan IPDU error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06: IPDU2 + Fan IPDU error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

07: All IPDU error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L30

L30

 

Detected indoor address

b6

¤

{

¤

SIM

Indoor outside interlock

Indoor

 

 

L31

 

 

 

 

Extended I/C error

I/F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

Page 23