Pentax MMK-AP0181H, MMK-AP0121H, MMK-AP0071H installation manual New check code, Special mention

Models: MMK-AP0071H MMK-AP0121H MMK-AP0181H

1 181
Download 181 pages 36.37 Kb
Page 25
Image 25
New check code

New check code

1. Difference between the new check code and the current system

The displaying method of the check code changes in this model and after.

 

Check code in current system

New check code

 

 

 

Used characters

Hexadecimal notation, 2 digits

Alphabet + Decimal notation, 2 digits

 

 

 

Characteristics of code classification

Few classification of communication/incorrect setup system

Many classification of communication/incorrect setup system

 

 

 

Block display

Indoor P.C. board, Outdoor P.C. board, Cycle, Communication

Communication/Incorrect setup (4 ways), Indoor protection,

Outdoor protection, Sensor, Compressor protection, etc.

 

 

 

 

 

<Display on wired remote controller>

[2.Special mention] goes on.

[UNIT No.] + Check code + Operation lamp (Green) flash

<Display on sensor part of wireless>

• Block display of combination of [Manual background] [Manual background] [Manual background]

<Display on indicater on wireless remote controller receiver part>

Unit No. and check code are displayed.

In a case of error with auxiliary code, check code and auxiliary code are displayed alternately.

→

Display

Classification

AUnused

CCentral control system error

ECommunication system error

FEach sensor error (Failure)

HCompressor protective system error

JUnused

LSetup error, Other errors

PProtective device operation

2.Special mention

1)If this model is connected to AI-NET by network adaptor, the different check codes are displayed on the main remote controller (New check code display on new remote controller) and AI-NET central control remote controller (Current system check code display on the current system central control remote controller).

2)The check code is displayed only while the air conditioner is operating (Remote controller start button ON).

When the air conditioner stops and the error is cleared, the check code display on the remote controller also disappears. However, if the error continues after stop of the operation, the check code is immediately displayed with restarting.

Network adaptor

AI-NET WORK bus

Indoor unit

OC

AI-NET central control

remote controller

F10

Main

remote controller

22

Page 25
Image 25
Pentax MMK-AP0181H, MMK-AP0121H, MMK-AP0071H installation manual New check code, Special mention