Indoor unit power supply (*1)

For the power supply of the indoor unit, prepare the exclusive power supply separated from that of the outdoor unit.

Arrange the power supply, earth leakage breaker, and main switch of the indoor unit connected to the same outdoor unit so that they are commonly used.

Power supply cord specification : Cable 3-core 2.5mm², in conformity with Design 60245 IEC 57.

Indoor/Outdoor inter-unit wiring, Central controller wiring

(*2) (*3)

2-core with polarity wires are used for the Indoor/Outdoor inter-unit wiring and Central controller wiring.

To prevent noise trouble, use 2-core shield wire.

The length of the communication line means the total length of the inter-unit wire length between indoor and outdoor units added with the central control system wire length.

Remote controller wiring

(*4)

2-core with non-polarity wire is used for wiring of the remote controller wiring and group remote controllers wiring.

Remote controller wiring, remote

Twist wire: 0.5mm2

to 2.0mm2 × 2

controller inter-unit wiring

 

 

 

 

 

Total wire length of remote controller

In case of wired type only

Up to 500m

wiring and remote controller inter-unit

 

 

In case of wireless type included

Up to 400m

wiring = L + L1 + L2 + … Ln

 

 

 

Total wire length of remote controller inter-unit wiring = L1 + L2 + … Ln

Up to 200m

 

 

 

CAUTION

The remote controller wire (Communication line) and AC220–240V wires cannot be parallel to contact each other and cannot be stored in the same conduits. If doing so, a trouble may be caused on the control system due to noise, etc.

Remote controller wiring

Indoor unit

 

Indoor unit

Indoor unit

Indoor unit

 

L1

 

L2

Ln

Remote

Remote controller inter-unit wiring

(Max. 8 units)

controller

 

 

 

 

 

Cable connection

REQUIREMENT

Be sure to pass the cable through the cable connection port of the indoor unit.

The low-voltage circuit is provided for the remote controller.

Tighten the screws of the terminal block, and fix the cables with cord clamp attached to the electric parts box.

(Do not apply tension to the connecting section of the terminal block.)

Main P.C. board

10

R

S

 

 

 

(L) (N)

 

R(L)

S(N)

 

 

 

 

 

Power supply

 

U1 U2 A B X Y

 

 

 

R(L)

S(N)

70

 

10

terminal block

 

 

 

50

 

 

 

 

 

2P

 

 

Earth line

Remote controller cable

Cord clamp

Connecting

Cord clamp

Power supply cable

 

 

cord

Inter-unit cable between indoor and outdoor units

12

Page 15
Image 15
Pentax MMK-AP0121H, MMK-AP0181H, MMK-AP0071H Cable connection, Indoor unit power supply *1, Remote controller wiring