Installation space

Reserve space required to install the indoor unit and for service work.

Keep 300mm or more for clearance between top plate of the indoor unit and the ceiling surface.

300 or more

300 or more

300 or more

The transport brackets are provided. Following to the table, remove the brackets according to direction of pipe. (Left, right, center) (For AP0071H to AP0181H, (left) and (right) transport brackets only are provided.)

Pipe side piping

Parts to be removed

 

 

Right side piping

Remove transport bracket (right) only.

 

Rear side piping

 

 

 

Left side piping

Remove all transport brackets.

 

 

REQUIREMENT

After removing of the transport brackets, do not apply force on the lower cabinet. It is to prevent deformation and breakage.

Pipe connecting position

<Front view>

• Remove the installation plate.

Installation plate

Transport bracket (Left)

Transport bracket (Center)

Transport bracket (Right)

(Including installation plate)

210

Top end of installation plate

77

Installation plate (Accessory)

24

 

 

Liquid side

 

Gas

368

 

side

 

50

75

76

60Left and

Drain pipe

110

right side piping

 

(Knockout hole)

 

 

Refrigerant pipe connecting port liquid side B

Refrigerant pipe connecting port gas side A

Ø20

380

450

Drain pipe

 

480

connecting port

 

<Bottom view>

Shipping from factory (Left side piping)

20

Gas pipe 440

Liquid pipe 540

Drain pipe 560

Model MMK-

A

B

 

 

 

AP0071H to AP0121H

Ø9.5

Ø6.4

 

 

 

AP0151H, AP0181H

Ø12.7

Ø6.4

 

 

 

AP0241H

Ø15.9

Ø9.5

 

 

 

4

Page 7