Installation of installation plate

To increase effect of drain, confirm the unit is installed horizontally or slightly lowering rightward viewed from the front side.

Lowering rightward viewed

Lowering leftward viewed

from the front side

from the front side

Horizontal installation

• Do not install the unit by plugging in the wall.

Indoor unit

The mass including installation plate of the indoor unit is shown in the following table. Check whether the wall has sufficient intensity.

Model MMK-

Mass (kg)

0071H to 0121H

20

0151H to 0181H

22

0241H

29

When installing the side plate, check the status that hook is inserted in square hole. Push in the side plate until it is stuck closely to the indoor unit.

Hook

Square hole

Screw cap

Side plate fixing screws

Installation of installation plate

Using the installation pattern, determine the installation position of the indoor unit, and drill the pipe hole matching with the position indicated in the installation pattern. When passing the refrigerant pipe through wall using metal mesh, be sure to use insulation sleeve such as polyvinyl chloride pipe.

„In case of wooden construction (Wide wall)

(1)Determine vertical position of the installation plate by interval (height) between the indoor unit and the ceiling.

(2)Determine the position so that screw hole of installation plate locates at the center of pillar or stud by adjusting left/right position without changing height of the installation plate.

(3)Tighten the screws (accessory parts) after bore preholes with a gimlet in the stud to prevent the crack.

„In case of reinforced concrete construction

(1)After drilling holes with interval by 150mm at the selected positions on the concrete wall, strike in grip anchor or hole-in anchor.

(2)Fix the installation plate to the anchor with bolt or nut. However, when using hole-in anchor, adjust drilling depth so that screw head-out is 10mm or less.

 

Hole-in anchor

Grip anchor

Nut

 

 

Bolt

screw

 

 

dia. Ø8

 

 

 

 

 

Installation plate

Installation

 

plate

10mm

 

Concrete

Concrete

 

 

or less

wall

 

 

wall

REQUIREMENT

Conduit tube may be buried in the concrete wall. Ask the constructor it.

Before installation of the indoor unit, be sure to check whether the installation plate has been completely installed.

„In case of rear direction piping

Using the installation pattern, determine the pipe hole position, and drill a pipe hole slightly lowering downward.