Maxos

Maxos standard trunking

The trunking fulfils two functions: first, it provides a sturdy in-line mounting rail on which to fix the electrical units, and second, it provides a housing for the electrical cables that bring power to the units.All the trunking sections are made of hot-dip galvanized steel with a white or silver finish and available in lengths of 1, 2 and 3 electrical units 36 W and 58 W.

A flat ribbon cable (5 or 7 wires) or two flat ribbon cables (2 x 5 or 2 x 7 wires) are integrated in the trunking and guarantee (in combination with an integrated phase selection switch and contact blocks) safe and correct cabling.The 7-wire cable is used to integrate light regulation or emergency lighting for those electrical units that are equipped with emergency battery packs. Double wiring (2 x 5 or 2 x 7 wires) is needed to provide a completely separate mains supply to the

electrical units. Double wiring is mostly used for emergency lighting by central emergency batteries or separate switching. Hence, no extra contact blocks or wiring are required.

For suspended light-lines, the trunking sections are connected using the integrated electrical connector and a sturdy external mechanical coupling piece (accessory). Surface-mounted light-lines use the same integrated electrical connector and an internal coupler (accessory).

On the upper part of the trunking section, special knock-out openings enable cable entry wherever needed.

The trunking is available with a complete range of interchangeable components that optimize flexibility.The outstanding stability of the sections and coupling pieces allows suspension intervals of 3.4 to 5 m (TL5) / 4.8 m (TL-D).

 

 

Maxos TL5

 

 

 

Maxos TL-D

 

 

Standard trunkings

 

 

 

Standard trunking

 

 

 

 

 

 

 

Type

 

4MX656

 

Type

 

4MX056

 

 

 

 

 

 

 

Length

 

1 x,2 x or 3 x length of electrical unit 49 W (491,

 

Length

 

1 x, 2 x or 3 x length of electrical unit of 58 W

 

 

492 or 493), for 80 and 35 W electrical units as

 

 

 

(581, 582 or 583) or 36 W (361, 362 or 363)

 

 

 

 

 

 

 

 

 

well

 

Electrical circuit option

 

1 x or 2 x flat ribbon cable, 5 or 7 wires:

 

 

1 x,2 x or 3 x length of electrical unit 54 W (541,

 

 

 

1 x or 2 x 5 x 1.5 or 2.5 mm² (1x5x2.5 etc)

 

 

542 or 543)

 

 

 

1 x or 2 x 7 x 1.5 or 2.5 mm² (1x7x2.5 etc)

 

 

 

 

 

 

 

Electrical circuit option

 

1 x or 2 x flat ribbon cable, 5 or 7 wires:

 

Material

 

Hot-dip galvanized steel in white (WH) or silver

 

 

1 x or 2 x 5 x 1.5 or 2.5 mm² (1x5x2.5 etc)

 

 

 

(SI)

 

 

1 x or 2 x 7 x 1.5 or 2.5 mm² (1x7x2.5 etc)

 

 

 

 

 

 

 

Accessory

 

Trunking end piece and mains connection set

 

 

 

 

 

 

 

Material

 

Hot-dip galvanized steel in white (WH) or silver

 

 

 

(9MX056 EP SET), trunking coupling pieces etc.

 

 

(SI)

 

 

 

(see chapter Maxos accessories)

 

 

 

 

 

 

 

Accessory

 

Trunking end piece, mains connection, trunking

 

Remarks

 

7-wire cable for integration of light regulation or

 

 

coupling pieces, etc. (see chapter Maxos

 

 

 

emergency lighting

 

 

accessories)

 

 

 

Double wiring for emergency lighting by central

 

 

 

 

 

 

 

Remarks

 

7-wire cable for integration of light regulation or

 

 

 

emergency batteries or separate switching

 

 

emergency lighting

 

 

 

 

 

 

 

 

 

 

 

 

Double wiring for emergency lighting by central

 

 

 

 

 

 

emergency batteries or separate switching

 

 

 

 

 

 

 

 

 

 

 

Where relevant, for detailed descriptions of Lighting Controls we refer you to chapter 11, and descriptions for e.g. optics/optical covers, lamps data, photometrical diagrams, etc. to the respective sections in chapter 12.

8.22

Light-line systems

Philips indoor luminaires

Page 23
Image 23
Philips TTX400 manual Maxos standard trunking