Chapter 1- Hardware Description

Listed fastening hardware must be compatible with the materials being joined and must be preclude loosening, deterioration and electrochemical corrosion of the hardware and joint materials.

Connecting the RMX 4000 to AC Power

Do not connect the green or green-yellow wire to the system single-point ground screw.

Customers are required to only use AC power cables supplied by Polycom.

The size of the protective earthing conductor should be a minimum of 10AWG.

All three outlets intended for connection of the three power cords must be protected with an external overcurrent protection device either in building or in the rack with the rating not higher than 20Amp.

Do not use an Extension cords with any of the cables.

1 Make sure that the power button is switched OFF on the RMX 4000.

ESD

connector

Ground

connector

 

 

 

Off/On switch

Power Entry Modules

2Insert the power cables into the power connectors on the rear panel of the RMX 4000.

1-18

Page 24
Image 24
Polycom DOC2559A manual Connecting the RMX 4000 to AC Power