18.0 Fault Finding

Refer to Section 16.0 “Illustrated Wiring Diagram” for position of terminals and components

Central Heating - Follow operational sequence (do

Turn selector switch to

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The display illuminates

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Error 110 flashing

 

 

 

 

 

YES

Error 130 flashing

 

 

 

 

 

Error 133 flashing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

Error 20, 28 or 50 flashing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

Error 119 flashing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn Central Heating

 

 

 

 

 

NO

thermostat to Maximum.

Pump runs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

Error 125 or 193 flashing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

3-way valve is open to Central

Heating circuit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

Fan runs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan runs at correct speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Spark at ignition electrodes for

NO

up to 5 seconds and for 3

 

 

 

attempts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Go to section ‘A’

 

Turn the selector switch to

YES

 

reset position for 5 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Go to section ‘E’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Go to section ‘C’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

Ensure all controls (and

 

YES

 

integral clock if fitted) are

 

 

calling for heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ensure that primary

 

 

 

 

 

circulation is OK & that

 

 

 

 

 

there is no blockage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Go to section ‘K’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Error 160 flashing

 

 

 

 

 

Go to section ‘D’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Error 160 flashing

 

 

 

 

 

Go to section ‘L’

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

Error 133 flashing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Go to section ‘F’

 

 

 

 

 

 

 

 

 

 

 

If the error 110 is still flashing.

Go to section ‘J’

Ensure controls are set to

demand and verify the

contacts are closed

Go to section ‘B’

Go to section ‘H’

Turn the selector switch to

reset

 

YES

Burner lights

 

 

 

YES

NO

Burner output modulates to maintain the temperature set

Burner does not stay alights

after 5 seconds

Check the Central Heating

NTC sensor

Go to section ‘E’

Error 130 flashing

Go to section ‘M’

YES

Error 133 flashing Go to section ‘I’

YES

Burner goes out

YES

Fan stops after 10 seconds

YES

Pump continues to run for 3

minutes

(room thermostat open)

YES

Operation sequence

successful