18.0 Fault Finding

Fault Finding Solutions Sections

A

B

Is there 230V at:

1.Main terminals L and N

2.Main terminal fuse

3.PCB - X1 connector terminals 1,2

Is there 230V at:

NO

NO

NO

Check electrical supply

Replace fuse

Check wiring

Display illuminated

NO

Replace PCB

C

1.

2.

1.

Pump

YES

If pump jammed, release

 

PCB - X3 connector terminals 3 & 4

YES

Change pump supply cable

CH system pressure less than 0.5 bar

NO

NO

Replace pump

 

NO

Replace PCB

 

YES

Re-pressurise system

 

Check connection water pressure

 

 

 

 

switch terminal

 

 

 

 

 

YES

Replace water

COM - NO and PCB connector

 

 

 

pressure switch

X400 terminals 3,4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.

Check the tap of the automatic air

NO

 

Open the automatic air vent

 

vent is opened

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D 1.

Fan connections correct at fan. PCB - X2 connector, is 230V AC across terminals 5 & 7

NO

YES

Fan jammed or faulty winding

Replace PCB

YES

Replace fan

© Baxi Heating UK Ltd 2012

57

Page 57
Image 57