Potthof & Co 33kw Flue Options, Total Equivalent Length =, A+B+C+1x90Bend, Vertical Flues, apart

Models: 24kw 28kw 33kw

1 64
Download 64 pages 28.28 Kb
Page 22
Image 22
Vertical

Vertical

Flues

1m Min toFlue OptionsTwin & Vertical Flue Systems (ii)

apartVertical FluesTotal Equivalent Length = (i)

IMPORTANT: All flue systems must be securely supported at least once every metre. Suitable pipe supports are available as accessories.

1m Min to

15m Max

 

8.0

Flue Options

 

 

8.2

Twin & Vertical Flue Systems

 

1. Maximum permissible equivalent flue lengths are:-

 

 

 

(60/100)

(80/125)

 

Vertical Concentric

10 metres

20 metres

 

Vertical Twin Pipe

15 metres

 

 

2. Any additional “in line” bends in the flue system must be

 

taken into consideration.

 

 

 

Their equivalent lengths are:-

 

 

Concentric Pipes:

 

 

 

 

135° bend

 

0.5 metres

 

 

93° bend

 

1.0 metres

 

Twin Flue Pipe

 

 

120mm Min

 

135° bend

 

0.25 metres

 

91.5° bend

 

0.50 metres

apart

 

 

 

The elbow supplied with the standard horizontal telescopic

 

flue kit is not included in any equivalent length calculations

Y

NOTE: Flue length is measured from point (i) to (ii) as

shown.

 

 

 

 

 

 

 

A+B+C+1x90°Bendjoint with the flue terminal (point Y). One 91.5°bend or two 135° bends can be included withoutreduction of the flue length.be reduced by the following amounts:-1 metre for each 91.5° bend (ii)

(i)

T

Vertical Flues

(Twin Pipe)

Total Equivalent Length =

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A+B+C+1x90°Bend

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Roof

All vertical and angled runs must be included,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

measured from the boiler adaptor (point X) to the

 

 

 

 

 

 

 

 

 

 

 

 

 

joint with the flue terminal (point Y). One 91.5°

 

 

 

 

 

 

 

 

 

bend or two 135° bends can be included without

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reduction of the flue length.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If further elbows are required the flue length must

 

 

 

 

 

 

 

 

 

be reduced by the following amounts:-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 metre for each 91.5° bend

(ii)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.5 metre for each 135° bend

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

This bend is equivalent to 1 metre

A

(i)

22© Baxi Heating UK Ltd 2012

600mm Min

 

Mini Terminal

apart

 

on Air Duct

 

 

 

 

(sited in loft)

 

 

 

 

 

 

 

 

 

 

 

1m Min

to

15m Max

Q

 

The total equivalent

 

length for this example

 

 

is

= 6.5 metres.

 

 

 

 

 

 

 

 

 

 

AIR DUCT

 

 

Equivalent

No of

Sub total

 

Length Value

 

fittings/pipes

 

 

1m extension

1m

 

5

 

5.0m

135°bend

0.25m

 

2

 

0.5m

 

 

 

 

 

 

91.5°bend

0.5m

 

2

 

1.0m

 

 

 

 

 

Equivalent Length Air Duct = 6.5m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLUE DUCT

 

 

Equivalent

No of

Sub total

 

Length Value

 

fittings/pipes

 

 

1m extension

1m

 

5

 

5.0m

135°bend

0.25m

 

2

 

0.5m

 

 

 

 

 

 

91.5°bend

0.5m

 

2

 

1.0m

 

 

 

 

 

Equivalent Length Flue Duct = 6.5m

 

 

 

 

 

 

Page 22
Image 22