Wall Thickness

(X)

Fig. 48

Flue Elbow

Apply Lubricant for ease of assembly.

Ensure Elbow is fully engaged into Boiler Adaptor

10.0Installation

10.7Fitting The Flue

HORIZONTAL FLUE

1.The standard flue is suitable for lengths between 100mm minimum and 685mm maximum, as measured from the edge of the flue elbow outlet to the joint between the terminal and air duct (Fig. 48).

2.Locate the flue elbow on the adaptor at the top of the boiler. Set the elbow to the required orientation (Fig. 50).

NOTE: The flue elbow is angled at 93 degrees to ensure a fall back to the boiler.

3.Measure the distance from the outside wall face to the elbow. This dimension will be known as ‘X’ (Fig. 51).

4.To dimension ‘X’ add 50mm. This dimension to be known as ‘Y’.

IMPORTANT: Check all dimensions before cutting.

5. Mark dimension ‘Y’ on the flue as shown (Fig. 52). Carefully cut the waste material from the flue, ensuring that

Adaptor

the ducts are square and free from burrs.

 

(X)

Fig. 51

Fig. 50

Wall Thickness

Waste

© Baxi Heating UK Ltd 2012

Y

Flue

Fig. 52

33

Page 33
Image 33