Table 6. Battery
Configuration 500VA: (1) 12V, 9 Ah internal battery
750VA: (2) 12V, 7 or 7.2 Ah internal batteries
1000VA: (2) 12V, 9 Ah internal batteries
1400VA: (3) 12V, 9 Ah internal batteries
Voltage 500VA: 12 Vdc
750-1000VA: 24 Vdc
1400VA: 36 Vdc
Type Sealed, maintenance free, valve regulated, lead acid
Charging Advanced charging for faster recovery; less than 3 hours to
90% usable capacity at nominal line and no supplementary
power supply load
Monitoring Advanced monitoring for earlier failure detection and warning
Table 7. Battery Run Times (in Minutes)
UPS Models by VARatings
Load (VA) Watts 500 750 1000 1400
200 128 17 38 41 58
300 192 11 27 28 41
500 320 5 14 15 28
600 402 - 9 10 19
750 503 - 6 8 14
900 603 - - 6 10
1000 670 - - 5 8
1200 804 - - - 6
1400 938 - - - 5
NOTE Battery times are approximate and may vary depending on the load configuration and battery charge.