Table 6. Battery

Configuration

500VA: (1) 12V, 9 Ah internal battery

 

750VA: (2) 12V, 7 or 7.2 Ah internal batteries

 

1000VA: (2) 12V, 9 Ah internal batteries

 

1400VA: (3) 12V, 9 Ah internal batteries

 

Voltage

500VA: 12 Vdc

 

750-1000VA: 24 Vdc

 

1400VA: 36 Vdc

 

Type

Sealed, maintenance free, valve regulated, lead acid

 

Charging

Advanced charging for faster recovery; less than 3 hours to

 

90% usable capacity at nominal line and no supplementary

 

power supply load

 

Monitoring

Advanced monitoring for earlier failure detection and warning

Table 7. Battery Run Times (in Minutes)

UPS Models by VA Ratings

Load (VA)

Watts

500

750

1000

1400

200

128

17

38

41

58

300

192

11

27

28

41

500

320

5

14

15

28

600

402

-

9

10

19

750

503

-

6

8

14

900

603

-

-

6

10

1000

670

-

-

5

8

1200

804

-

-

-

6

1400

938

-

-

-

5

NOTE Battery times are approximate and may vary depending on the load configuration and battery charge.

Powerware

®

5115A USB User’s Guide www.powerware.com.au

23

 

 

Page 29
Image 29
Powerware 5115A USB manual Battery Run Times in Minutes