Quadra-Fire SAPPHIRE-D-PMH Step, Fire Risk Exhaust Fume Risk, Impaired Performance of Appliance

Models: SAPPHIRE-D-CSB SAPPHIRE-D-PMH SAPPHIRE-MBK SAPPHIRE-D-MBK

1 52
Download 52 pages 31.54 Kb
Page 14
Image 14
Burn Risk.

(NOTE: Some termination caps may cause the vent pipe to be off center on flashing). Ensure that proper clearances to combustible materials are maintained. If you are not using an approved termination cap with a built-in standoff on a building with vinyl siding, a vinyl siding standoff should be installed between the termination cap and the exterior wall (Figure 5.9). Follow manufacturer’s instructions for attaching the vinyl siding standoff to the horizontal termination cap. The vinyl siding standoff prevents excessive heat from possibly melting the vinyl siding material. . Remove siding from the area where the standoff will be located.

WARNING! The vent terminal cap shall not be recessed into a wall or siding

1/4 in. (6mm) Manual background

Fold Strap HereManual background

Sheet Metal Screw

Wall Thimble Cover/Ceiling

Firestop as Required by Local

JurisdictionStrap

Figure 5.10

Wall Thimble

Figure 5.9

Wall Thimble Cover

Wall Thimble

Vinyl Siding

Apply sealant to all four sides

Manual background Screws

Manual background Bolt horizontal top to vinyl standoff

Manual backgroundManual backgroundManual backgroundManual background Screws

Vinyl siding standoff with siding beneath removed

Note: The attachment from the vent pipe to the vent cap must be sealed with silicone. Venting terminals shall not be recessed into a wall or siding.

Manual background WARNING

Fire Risk.

Exhaust Fume Risk.

Impaired Performance of Appliance.

Ensure vent components are locked together correctly.

Pipe may separate if not properly joined.

Step 5.

Place the wall thimble cover over the pipe assembly and slide the appliance and vent assembly towards the wall, carefully inserting the vent pipe into the vent termination cap assembly. It is important that the vent pipe extend into the vent termination cap a sufficient distance so as to result in a minimum pipe overlap of 1-1/4 in. (32mm). Secure the connection between the vent pipe and the vent termination cap by attaching the two sheet metal strips extending from the vent termination cap assembly into the outer wall of the vent pipe. Use the two sheet metal screws provided to connect the strips to the pipe section. Figure 5.10.

Manual background WARNING

Do NOT connect a pipe section to a termination cap without using the telescoping flue section found on the termination cap.

Manual background WARNING

Burn Risk.

Local codes may require installation of a cap shield to prevent anything or anyone from touching the hot cap.

14

Quadra-Fire • Sapphire • 7055-116 Rev. D • 6/11

Page 14
Image 14
Quadra-Fire SAPPHIRE-D-PMH, SAPPHIRE-MBK Step, Fire Risk Exhaust Fume Risk, Impaired Performance of Appliance, Burn Risk