Quadra-Fire SAPPHIRE-D-CSB, SAPPHIRE-MBK G.Vertical Termination, Direct Vent Pipe, Step

Models: SAPPHIRE-D-CSB SAPPHIRE-D-PMH SAPPHIRE-MBK SAPPHIRE-D-MBK

1 52
Download 52 pages 31.54 Kb
Page 15
Image 15
G.Vertical Termination

G.Vertical Termination

1.Direct Vent Pipe

WARNING

Fire Risk. Explosion Risk.

Maintain vent clearance to combustibles as speci- fied.

• Do not pack air space with insulation or other

Storm

Collar

Firestop 1.Direct Vent PipeManual background

Manual backgroundVertical Termination Cap

Flashing

Manual backgroundManual backgroundSupport

Box

materials.

Failure to keep insulation or other materials away from vent pipe may cause fire.

Pipe Length

Figure 5.11

Step 1.

Check the installation instructions for required 1 in. (25mm) clearances (air space) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, or other nearby combustible surfaces. Figure 5.17 on page

17.Check the instructions below for maximum vertical rise of the venting system, and any maximum horizontal offset limitations. All offsets must fall within the set parameters of the vent graph Figure 5.2 on page 11.

NOTE: Maximum vertical rise allowable is 40 ft. (12m) Figure 5.11.

NOTE: Maximum number of 45° elbows permitted for a vertical installation is eight, provided their installation does not decrease maximum allowable horizontal run (as specified by vent graph, on page 11).

40 ft. (12.19m) Manual background Maximum

Figure 5.12

Step 2.

Set the gas appliance in its desired location. Drop a plumb bob down from the ceiling to the position of the appliance flue exit, and mark the location where the vent will penetrate the ceiling. Drill a small hole at this point. Next, drop a plumb bob from the roof to the hole previously drilled in the ceiling, and mark the spot where the vent will penetrate the roof. Determine if ceiling joists, roof rafters, or other framing will obstruct the venting system. You may wish to relocate the appliance, or to offset, as shown in Figure 5.13 on page 16, to avoid cutting loadbearing members. When location is determined, drill small hole.

Quadra-Fire • Sapphire • 7055-116 Rev. D • 6/11

15

Page 15
Image 15
Quadra-Fire SAPPHIRE-D-CSB, SAPPHIRE-MBK, SAPPHIRE-D-MBK, SAPPHIRE-D-PMH G.Vertical Termination, Direct Vent Pipe, Step