Setup Menu

The Setup menu allows you to set some of the UPS operating parameters. The parameters that can be set include the following;

Setup Menu Menu Scroll

Audio Alarm xxx Menu xxx Scroll

AC Output xxx

Mernu xxx Scroll

Auto Test xxx Menu xxx Scroll

Auto Restart xxx Menu xxx Scroll

Report Msgs xxx Menu xxx Scroll

Note: At any step in the “Setup” menu, pressing the “MENU” selection will move you to the “Config” menu.

Audio Alarm xxx : Turn the Audible Alarm on or off. If the Alarm is OFF, the beeper will NOT sound during an alarm condition. The normal condition is ON.

AC Output xxx : Turn the AC output on or off. If the AC Output is turned OFF, no power will be supplied to your equipment. The normal condition is ON. Whenever the UPS power switch is turned on, this parameter is reset to ON.

Auto Test xxx : Turn the Auto-test mode on or off. If the Auto-test mode is OFF, periodic checks running under battery power will NOT be performed. If Auto-test is ON, then every 14 days the system will check the status of the system and run the power from the battery for about 10 seconds. The normal condition is ON.

Auto Restart xxx : Turn the Auto-restart on or off. If Auto-restart is ON, AND the UPS turned itself off because of a low battery condition, the UPS will automatically restart after AC power is restored to the unit. Otherwise, after a low battery shutdown condition has occurred, the UPS will not restart and the condition of the fault will be displayed. The normal condition is ON.

Report Msgs xxx : Turn the Report messages on or off. If the Report Msgs is turned ON, then the messages will be immediately displayed when a condition exists. If the Report Msgs is OFF then the messages will not be immediately displayed, but will be displayed when you cycle through the STATUS menu. The normal condition is turned ON.

22