INITIAL ERROR MESSAGES

As soon as the UPS is first turned on, it performs a series of self tests. If the self tests fail then the UPS will report the failure and display the fault. If the self test passes, but the UPS was shut down previously due to a fault, the previous fault code or message will be displayed. This feature allows you to determine why the UPS shut down. The LCD screen will display the words “Error Detected” on the top line of the screen, and one of the messages in the Error Code list is shown on the second line.

Model XRT600 LED Display Error Codes

Displayed in binary code

LED

 

 

DISPLAY

POSSIBLE CAUSE

ACTION TO TAKE

ooox

Low ac input

Verify incoming ac

ooxo

Input ac to high

Verify incoming ac

ooxx

Input AC frequency out of

Verify incoming freq. for this

 

range for unit.

model.

oxoo

Excessive output current

Verify output load

 

being drawn

matches unit.

oxox

Fan not running

Verify nothing has

 

 

gotten into the fan

oxxo

Fan or air

Clear air passages

 

passages blocked

 

oxxx

Battery pack is bad or

Check battery voltage

 

disconnected

and connections

xooo

UPS has had a

Call for service

 

hardware fault

 

xoox

Output voltage

Call for service

 

is too high

 

xoxo

Output voltage

Call for service

 

is too low

 

On the XRT600, these messages can be cleared by pressing the Test/Alarm Silence button.