6. TROUBLESHOOTING

If your XRT UPS does not function as you expect or if you get an error code or message, please follow the chart outlined below before calling your dealer or Minuteman. Make note of each problem so that we may quickly troubleshoot and correct the problem. Please remember to have your model and serial number before calling.

TROUBLESHOOTING

SYMPTOM

POSSIBLE CAUSE

ACTION TO TAKE

No lights/menu, no alarm

Front panel switch in off

Turn on switch.

(UPS not ON)

position.

Reset circuit breaker.

Rear panel circuit breaker

Check utility input

 

 

tripped.

power.

 

No incoming utility.

 

 

 

 

Low AC is indicated, and

Incoming AC is < 75% of

On LED front panel,

UPS is not supplying power

nominal and >72% of

press TEST/ALARM

nomimal

SILENCE switch.

 

 

 

On LCD front panel,

 

 

press any button to go

 

 

to the battery mode.

No output, some LED’s are

This is an error code, and

Look up the message or

on, or the LCD shows error

there are many different

error code, and take the

causes.

appropriate action

message.

 

and/or call for service.

 

 

 

 

 

Backup time is less than the

Battery not fully charged.

Recharge batteries for

rating

1 or more dead batteries.

at least 8 hours. If

 

Load is greater than

problem persists, call for

 

estimated.

service. Verify load is

 

Charger failure.

 

correct.

 

 

The UPS appears to be

Output turned off by

Select STATUS menu,

working, but has no output

computer or external control.

and search for OUTPUT

 

OFF message. Turn on

voltage

 

 

with SETUP menu or

 

 

 

 

cycle Power Switch.

 

 

Verify remote OFF

 

 

contact / switch is off.

UPS beeps continuously

Imminent shutdown pending.

Look up the message or

 

Error code will be displayed.

error code, and take the

 

 

appropriate action

 

 

and/or call for service.