REMOTE DIRECT COMMUNICATIONS

Pin 1:

 

Not Used

Pin 2:

LBW

Output signal from UPS (RS232 levels)

 

 

High signal (+3 to +12 volts)= Low

 

 

Battery Warning

Pin 3:

UPS Shutdown

Input signal to UPS, Shuts down

 

 

UPS (RS232 levels)

 

 

High signal (+3 to +12 volts) = UPS OFF

Pin 4:

AC Fail NO.

Output signal from UPS, open

 

 

collector, High impedance = AC OK

 

 

Low impedance to ground = AC Failed

Pin 5:

Ground

Common Return

Pin 6:

Low Battery Warning

Output signal from UPS, open

 

 

collector

 

 

High impedance = OK

 

 

Low impedance to ground = Low

 

Battery Warning

Pin 7:

AC Fail NC

Output signal from UPS, open

 

 

collector High impedance = AC Failed

 

 

Low impedance to ground = AC OK

Pin 8:

AC Fail Logic Signal

Output signal from UPS, logic level

 

 

Logic High (+3 to +12 volts) =

 

 

AC failed

 

 

Logic Low (0 volts) = AC OK

Pin 9:

Remote Shutdown

Input signal to UPS, pulled to 5

 

 

VDC through 10 K ohms

 

 

>2.4 VDC = Normal output

 

 

<0.8 VDC = Output off

38

Page 39
Image 39
Rackmount Solutions XRT Series manual Remote Direct Communications, Lbw