7. GENERAL PRODUCT SPECIFICATIONS

 

XRT600

 

XRT1000

XRT1500

XRT2000

 

XRT2001

XRT2002

 

(XRT600/2)

(XRT1000/2)

 

(XRT2000/2)

 

 

 

Acceptable input

92-140v

 

92-140v

92-140v

92-140v

 

176-278v

152v-267v

volts

(169-268v)

 

(169-268v)

N/A

(169-268v)

 

 

 

Output Voltage

120v

 

120v

120v

120v

 

120v/240v

120/208v

(on-line) +/- 10%

(230v)

 

(230v)

N/A

(230v)

 

 

 

Nominal input

60 Hz

 

60 Hz

60 Hz

60 Hz

 

60 Hz

60 Hz

frequency

(50 Hz)

 

(50 Hz)

N/A

50 Hz

 

 

 

Input protection

 

 

 

Reset-able circuit breaker

 

 

Frequency limits

 

 

 

60 Hz. +/- 3 Hz

 

 

(online)

 

 

 

(50 Hz. +/- 3 Hz. )

 

 

Transfer time

 

 

 

4 ms Typical

 

 

Max load

600 /600

 

1000 / 1000

1500 / 1500

2000 / 2000

 

2000 / 2000

2000 / 2000

(VA/watts)

 

 

 

 

 

 

 

 

On Battery

120v

 

120v

120v (N/A)

120v (230v)

 

120v /

120v /

Output Voltage

(230v)

 

(230v)

 

 

 

240v

208v

 

 

 

 

 

 

 

On Battery

60 Hz +/-0.1 Hz. Unless synchronized to utility during brownout.

frequency

(50 Hz +/- 0.1 Hz. Unless synchronized to utility during brownout)

On Battery

 

 

 

Low distortion sine wave

 

 

waveform

 

 

 

 

 

 

 

 

Protection

Over-current and short circuit protected: latching shutdown on overload

Surge energy

 

480 joules: one time 10 to 1000μ s waveform ( 120 VAC units )

rating

 

 

 

 

 

 

 

 

Surge current

6500A maximum: one time 8 to 20 μ s waveform (120 VAC units )

capability

 

 

 

 

 

 

 

 

Surge response

 

 

0 Ns (instantaneous) normal mode, <5 Ns common mode

 

time

 

 

 

 

 

 

 

 

Surge volts let

 

 

 

< .2%

 

 

 

thru

 

 

 

 

 

 

 

 

Noise filter

Normal and common mode EMI /RFI suppression, 100 kHz to 10 MHz

Battery type

 

 

Spill proof, sealed, maintenance free, lead-acid

 

Typical battery

 

 

 

5 years

 

 

life

 

 

 

 

 

 

 

 

Typical recharge

 

 

4 hours for a single battery pack

 

 

time

 

 

 

 

 

 

 

 

Operating temp

 

 

 

0 to 40°C (+32 to 104°F)

 

 

Operating &

 

 

 

0 to 95% non-condensing

 

 

storage relative

 

 

 

 

 

 

 

 

humidity

 

 

 

 

 

 

 

 

Storage

 

 

 

-15 to +45°C (+5 to 113°F)

 

 

temperature

 

 

 

 

 

 

 

 

Operating

 

 

0 to 3000 meters ( 0 to 10,000 ft. )

 

 

elevation

 

 

 

 

 

 

 

 

Electromagnetic

 

 

IEC 801-2, 801-3, 801-4: Severity level 5

 

immunity

 

 

 

 

 

 

 

 

Audible noise

 

 

 

<45 dB @ 1 meter

 

 

Audible Alarm

 

 

On overload, On battery, Low battery warning, check fan

 

Communication

 

 

 

DB-9 Minuteman standard

 

 

s port

 

 

 

 

 

 

 

 

35