TIME SCHEDULE
TS TIME SCHEDULE This is a
(no days) on all settings. Changes can be made to accommodate individual schedules.
SUPPLY TEMPERATURE
The RayTemp control strategy closely matches water temperature to demand as hot water use varies throughout the day. The setpoint is adjusted based on a demand profile which is recorded for the last seven days. The RayTemp scans this profile and adjusts the setpoint in anticipation of demand. This strategy is complemented with a
C0 SELECT - Maximum Regular Temperature During Regular periods the desired temper- ature will be set between (screen) C0 and C1 according to demand. The time clock schedule deter- mines when Regular takes effect. Default Temp 140°F.
C1 SELECT - Minimum Regular Temperature The supply temperature will not be set below this value during Regular periods. Default Temp 130°F.
C2 SELECT - Maximum Peak Temperature C2 and C3 become the new maximum and min- imum temperatures when the time clock schedule is in Peak mode. Default Temp 140°F.
C3 SELECT - Minimum Peak Temperature During peak periods the supply temperature will not be set below this value. Default Temp 130°F.
C4 SELECT - Maximum Laundry Temperature C4 and C5 will be the maximum and mini- mum temperatures in effect if Laundry is activated by the
C5 SELECT - Minimum Laundry Temperature See C4 above. Default Temp 140°F.
19