Hint: Apply sealant to female end.

INSTALLATION

NOTE: For Snorkel terminations in ABOVE grade installations, follow national or local code requirements.

Below Grade Snorkel Installation

If the Snorkel Termination must be installed below grade, i.e. basement application, properdrainagemustbeprovidedtoprevent waterfromenteringtheSnorkelTermination. Refer to Dura-Vent Installation instructions for details.. Do not attempt to enclose the Snorkel within the wall, or any other type of enclosure.

4)Install wall penetration heat shield in the center of the 9-1/2" round hole and attach with wood screws. The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings. Diagram 3.

Diagram 3

5)If installing termination on a siding covered wall, a vinyl siding standoff or furring strips must be used to ensure that the termination is not recessed into the siding. Diagram. 3.

6)Take the Riser Vent terminal and separate the Backing Plate from the Riser Vent Front by removing 8 screws as shown in diagram 4.

7)Install the Backing Plate into the wall penetration heat shield and attach using 4 screws. Diagram 4.

8)Connect all pipe sections to unit and install into wall:

a)Measure pipe length required and cut to length. Hint: use the cut end of the 6-5/8" dia. outer pipe at the fl ue terminal end.

b)Push the pipe sections completely together, the minimum pipe overlap is 1-1/4". Secure all outer pipe joints by using at least two screws. Locate the screws at the bottom of the pipe so that the screw heads are hidden on the fi nal installation. Apply seal- ant "Mill-Pac" to inner pipe and high temp silicone sealant or "Mill-Pac" to outer pipe on every joint.

Hint: Apply sealant to female end.

c)Before connecting the fl ue pipe to the fl ue termination, slide the black decorative wall thimble cover over the fl ue pipe, then slide the Wall Penetration Heat Shield (Part # 946-202)overthefluepipe.Diagram 3.

d)Slide the appliance and fl ue assem- bly towards the wall carefully insert- ing the fl ue pipe into the riser vent terminal assembly. It is important that the fl ue pipe extends into the Riser Vent Backing Plate a sufficient distancesoastoresultinaminimum pipe overlap of 1-1/4 inches. Secure theconnectionbetweenthefluepipe and the flue cap by attaching the two sheet metal strips extending from the Riser Vent Backing Plate into the outer wall of the fl ue pipe. Use two aluminum screws provided to con- nect the strips to the pipe section. Bend any remaining portion of the sheet metal strip back towards the flue cap and cut off any excess, it will be concealed by the decorative wall thimble cover. See diagram 5.

8)Slide the decorative wall thimble up to the wall surface being careful not to scratch the paint. See diagram 5.

Diagram 5

9)Back outside: Apply sealant to the 4" inner fl ue and slide the Riser Vent Front into the Backing Plate and fasten with 8 screws.

IMPORTANT:

When connecting the pipe to the Riser Vent, apply Mill-Pac to the inner pipe on theRiserVentTerminal,aroundthebead. Ensure that the flue pipe is pushed past the bead for a secure fit.

10)Seal around the outer edge of the Riser Vent Backing Plate.

Diagram 4

F37 Regency® Rear Flued Room Sealed Freestanding Gas Heater

11

Page 11
Image 11