Regency G36D-LP PROPANE Installation, Termination Locations, Vent terminal, Air supply outlet

Models: G36D-NG NATURAL GAS G36D-LP PROPANE

1 40
Download 40 pages 45.99 Kb
Page 10
Image 10
Vertical Termination

10

Vertical Termination

24"

D

E

V

Inside corner detail

G VerticalVENT

V

A

Vertical

Termination

24"

18"

V

EXTERIOR

INSTALLATION

B

V

M

.

C

 

V

Fixed

 

 

Closed

F

V

Openable

 

B

V

Openable

B

Fixed Closed

 

H

V

 

B

N

 

L

VENT

B

B

V

K

A

 

j

 

 

 

A

 

V

A

V

Vent terminal

A

Air supply outlet

 

Area where terminal is not permited

 

 

 

 

UltraGlow G36D Zero Clearance Direct Vent

A= Clearance above grade, veranda, porch, deck, or balcony *(min. 12"/30cm) B= Clearance to window or door that may be opened *(12"/30cm) #(9"/23cm) C= Clearance to permanently closed window *(min. 12"/30cm)

D= Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of (24"/60cm) from the centerline of the terminal (min. 18"/46cm) check with local code.

E= Clearance to unventilated soffit (min. 15"/38cm)

F= Clearance to outside corner: with AstroCap Termination Cap (min. 6"/15cm), with Dura-Vent Termination Cap (14"/36cm)

G= Clearance to inside corner: with AstroCap Termination Cap (min. 6"/15cm), with Dura- Vent Termination Cap (12"/30cm)

H= Not to be installed above a meter/regulator assembly within (3'/90cm) horizontally from the centerline of the regulator.

J= Clearance to service regulator vent outlet *(min. 36"/90cm)

K= Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance *(12"/30cm) #(9"/23cm)

L= Clearance to a mechanical air supply inlet *(min. 72"/1.8m) #3' (91cm) above if with in 10' (3m) horizontally.

M= Clearance above paved sidewalk or a paved driveway located on public property *(min. 84"/2.1m)

N= Clearance under veranda, porch, deck, or balcony *(min. 12"/30cm)

TERMINATION LOCATIONS

Gas Fireplace

Note:

-A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.

-Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

-If the vent termination is accessible, a certified guard shall be installed.

*As specified in CGA B149 Installation Code. Note: Local codes or regulations may require different clearances.

# In accordance with the current ANSI Z223.1/NFPA 54 ,National Fuel Gas Code.

Page 10
Image 10
Regency G36D-LP PROPANE Installation, Termination Locations, Vent terminal, Air supply outlet, Vertical Termination